SPECIFICATIONS
1.6.1
Technical
1.6.2
External Connections
Terminal blocks located on the rear of the chassis suitable for #14 square tongue lugs.
Wiring to FT-10 switches suitable for #12 wire lugs.
1.6.3
Contact Rating Data
Trip rated contacts - make & carry 30 amps for 1 second, 10 amps continuously, and break 50
watts resistive or 25 watts with L/R =0.045 seconds. Trip rated contacts are:
• Trips A1, A2
• Programmable Contact OC1
• Close outputs Close 1, Close 2
All other output contacts are non-trip rated - make and carry 3 amps continuously, and break
0.1 amps resistive.
Operating Speed
(from fault detection to trip contact close (60 Hz)
ac Voltage (V
Ln
)
ac Current (I
n
)
Rated Frequency
Maximum Permissible ac Voltage (Thermal Rating)
• Continuous
• 10 Second
Maximum Permissible ac Current (Thermal Rating)
• Continuous
• 1 Second
Minimum Operating Current
dc Battery Voltages
Nominal
48/60 Vdc
110/125 Vdc
220/250 Vdc
dc Burdens: Battery
ac Burdens:
Voltage input
Current input
12 msec (minimum)
26 msec (typical)
60 Hz 70
Volt rms
50 Hz 63.5 Volt rms
1 or 5 Amp
50 or 60 Hz
1.5 x V
Ln
2.5 x V
Ln
3 x I
n
100 x I
n
0.1 x I
n
Operating Range
38-70 Volt dc
88-145 Volt dc
176- 290 Volt dc
7 Watts normal
30 Watts tripping
0.02 VA at 70 Vac/phase
0.15 VA at 5 A/phase