I.L. 40-386.4
4-19
Zone1 Delay Trip Timer
T1 Timer
T1
0 - 15 cycles
0 - 15 CYCL
Zone2 Phase Unit
Zone2 Ø
Z2P
Disabled/0.01 - 50.00 OHMS
OUT/0.01-50.00
OHMS
Zone2 Phase Timer
– Timer Type
– Definite Time
– Torque Control CO
Curve
(with Time Delay
or Inst. Reset)
– Torque Control
Pickup
– Torque control
Time Curve
T2Ø Type
T2Ø Time
T2Ø CV
T2Ø PkUp
T2Ø TC
Z2PT
T2P
TP2CV
T2PPU
T2PTC
Blocked/Definite Time/Torque Con-
trol
0.10 - 2.99 sec
CO-2/C0-5/C0-6/CO-7 /CO-8/CO-
9/CO/11
Each w/Reset or Inst
0.50 - 10.00 Amps
1 - 63
DISAB/DEFTM/TORQ
0.100 - 2.99 SEC
CO-2/5/6/7/8/9/11 I/R
0.500 - 10.00 AMPS
1 - 63
Zone2 Ground Unit
Zone2 G
Z2G
Disabled/0.01 - 50.00 OHMS
OUT/0.01-50.00
OHMS
Zone2 Ground Timer
–Timer Type
– Definite Time
– Torque Control CO
Curve
(with Time Delay
or Inst. Reset)
– Torque Control
Pickup
– Torque Control
Time Curve
T2G Type
T2G Time
T2G CV
T2G Pickup
T2G TC
Z2GT
T2G
T2GCV
T2GPU
T2GTC
Blocked/Definite Time/ Torque Con-
trol
0.10 - 2.99 Sec
CO-2/CO-5/CO-6/CO-7/CO-8/CO-
9/CO-11
Each w/Reset or Inst
0.50 - 10.00 Amps
1- 63
DISAB/DEFTM/TORQ
0.100 - 2.99 SEC
CO-2/5/6/7/8/9/11 I/R
0.500 - 10.00 AMPS
1- 63
Zone3 Phase Unit
Zone3 Ø
Z3P
Disabled/0.01 - 50.00 OHMS
OUT/0.01-50.00
OHMS
Zone3 Phase Timer
T3 Ø
T3P
Blocked/0.10 - 9.99 Sec
BLK/0.10 - 9.99 SEC
Zone3 Ground Unit
Zone3 G
Z3G
Disabled/0.01 - 50.00 OHMS
OUT/0.01-50.00
OHMS
Zone3 Ground Timer
T3 G
T3G
Blocked/0.10 - 9.99 Sec
BLK/0.10 - 9.99SEC
Zone3 Direction
Zone3
Z3FR
Forward Dir.
Reverse Dir.
FWD
REV
Pos. Seq. Line Imped-
ance Angle
Ang Pos.
PANG
10 - 90
O
10 - 90 DEG
Zero Seq. Line
Impedance Angle
Ang Zero
GANG
10 - 90
O
10 - 90 DEG
Z0L/Z1L
Z0L/Z1L
ZR
0.1 - 10.0
0.100 - 10.00
Low Voltage Unit
Low V
LV
40 - 60 Volts
40 - 60 VOLTS
Overcurrent Units:
– Low Set Phase
– Medium Set Phase
– Low Set Ground
– Medium Set
Ground
– High Set Phase
– High Set Ground
Low I Ø
IM
3I0s
3I0m
Inst. Ø
Inst. G
IL
IM
IOS
IOM
ITP
ITG
0.50 - 10.00 Amps
0.50 - 10.00 Amps
0.50 - 10.00 Amps
0.50 - 10.00 Amps
Disabled/ 2.0 - 150.0 Amps
Disabled/ 2.0 - 150.0 Amps
0.500 - 10.00 AMPS
0.500 - 10.00 AMPS
0.500 - 10.00 AMPS
0.500 - 10.00 AMPS
OUT/ 2.00-150.0
AMPS
OUT/ 2.00-150.0
AMPS
Out-of-Step Block
OS Block
OSB
Yes/No
YES/NO
OSB Override Timer
OSOT
OSOT
400 - 4000 msec
400 - 4000 msec
Setting
Function Field
Value Field
Front
Panel
RCP
Front Panel
RCP
SET