![background image](http://html1.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_product-manual_3389474064.webp)
Table 44. Autorecloser SMBRREC
Function
Range or value
Accuracy
Number of autoreclosing shots
1 - 5
-
Autoreclosing open time:
shot 1 - t1 3Ph
(0.000-60.000) s
± 0.5% ± 25 ms
shot 2 - t2 3Ph
shot 3 - t3 3Ph
shot 4 - t4 3Ph
shot 5 - t5 3Ph
(0.00-6000.00) s
Autorecloser maximum wait time for sync
(0.00-6000.00) s
Maximum trip pulse duration
(0.000-60.000) s
Inhibit reset time
(0.000-60.000) s
Reclaim time
(0.00-6000.00) s
Minimum time CB must be closed before AR
becomes ready for autoreclosing cycle
(0.00-6000.00) s
CB check time before unsuccessful
(0.00-6000.00) s
Wait for master release
(0.00-6000.00) s
Wait time after close command before
proceeding to next shot
(0.000-60.000) s
Logic
Table 45. Tripping logic SMPPTRC
Function
Range or value
Accuracy
Trip action
3-ph
-
Timers
(0.000-60.000) s
± 0.5% ± 10 ms
Bay control REC650
1MRK 511 249-BEN -
Product version: 1.1
Issued: February 2011
64
ABB
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 Product Guide...
Page 81: ...81...