![background image](http://html1.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_product-manual_3389474063.webp)
Table 42. Breaker close/trip circuit monitoring TCSSCBR
Function
Range or value
Accuracy
Operate time delay
(0.020 - 300.000) s
± 0,5% ± 110 ms
Control
Table 43. Synchronizing, synchrocheck and energizing check SESRSYN
Function
Range or value
Accuracy
Phase shift,
j
line
-
j
bus
(-180 to 180) degrees
-
Voltage ratio, U
bus
/U
line
0.2 to 5.0
-
Frequency difference limit between
bus and line
(0.003-1.000) Hz
± 2.0 mHz
Phase angle difference limit
between bus and line
(5.0-90.0) degrees
± 2.0 degrees
Voltage difference limit between
bus and line
± 0.5% of U
r
Time delay output for synchrocheck (0.000-60.000) s
± 0.5% ± 25 ms
Time delay for energizing check
(0.000-60.000) s
± 0.5% ± 25 ms
Closing time for the circuit breaker
(0.000-60.000) s
± 0.5% ± 25 ms
Bay control REC650