![background image](http://html1.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_product-manual_3389474045.webp)
Table 8. Ethernet interfaces
Ethernet interface
Protocol
Cable
Data transfer rate
LAN/HMI port (X0)
1)
-
CAT 6 S/FTP or better 100 MBits/s
LAN1 (X1)
TCP/IP protocol
Fibre-optic cable
with LC connector
100 MBits/s
1) Only available for the external HMI option.
Table 9. Fibre-optic communication link
Wave length
Fibre type
Connector
Permitted path
attenuation
1)
Distance
1300 nm
MM 62.5/125
μm glass
fibre core
LC
<8 dB
2 km
1) Maximum allowed attenuation caused by connectors and cable together
Table 10. X4/IRIG-B interface
Type
Protocol
Cable
Screw terminal, pin
row header
IRIG-B
Shielded twisted pair cable
Recommended: CAT 5, Belden RS-485 (9841-
9844) or Alpha Wire (Alpha 6222-6230)
Table 11. Serial rear interface
Type
Counter connector
Serial port (X9)
Optical serial port, type ST for IEC
60870-5-103
Influencing factors
Table 12. Degree of protection of flush-mounted IED
Description
Value
Front side
IP 40
Rear side, connection terminals
IP 20
Table 13. Degree of protection of the LHMI