Table 5. Signal output and IRF output
IRF relay change over - type signal output relay
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
10 A
Make and carry 0.5 s
30 A
Breaking capacity when the control-circuit
time constant L/R<40 ms, at U< 48/110/220
V DC
≤0.5 A/≤0.1 A/≤0.04 A
Table 6. Power output relays without TCS function
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit
time constant L/R<40 ms, at U< 48/110/220
V DC
≤1 A/≤0.3 A/≤0.1 A
Table 7. Power output relays with TCS function
Description
Value
Rated voltage
250 V DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit
time constant L/R<40 ms, at U< 48/110/220
V DC
≤1 A/≤0.3 A/≤0.1 A
Control voltage range
20...250 V DC
Current drain through the supervision circuit ~1.0 mA
Minimum voltage over the TCS contact
20 V DC
Bay control REC650
1MRK 511 249-BEN -
Product version: 1.1
Issued: February 2011
44