Figure 29: Outputs group
Seq. Start
Settings
Functional settings
Start / Stop
Protections
Warnings
Faults
Inputs
Outputs
Fieldbus
7:2.4.6 Outputs
To set parameters related to the programmable outputs, enter the Outputs group.
Relay K4
Select the required function for output relay K4.
One of the following functions can be selected:
Run Run indication.
TOR Top of ramp indication.
Event Indication of selected event(s) . The following events can be selected individually:
• Motor overload protection
• Shunt fault
• Fault
• Low current warning
• High current protection
• High current warning
• SCR overload protection
• SCR overload warning
• Locked rotor protection
• Overload warning
• Underload protection
• Phase reversal protection
• Phase imbalance protection
• PTC protection
Press
Store
to save/activate the selected function.
Relay K5
Select the required function for output relay K5.
One of the following functions can be selected:
Run Run indication.
TOR Top of ramp indication.
Event Indication of selected event(s), see relay K4.
Press
Store
to save/activate the selected function.
Relay K6
Select the required function for output relay K6.
One of the following functions can be selected:
Run Run indication.
TOR Top of ramp indication.
Event Indication of selected event(s), see relay K4.
Press
Store
to save/activate the selected function.
SW Outp V7
Select the required function for the fieldbus communication output SW Outp V7.
One of the following functions can be selected:
Run Run indication.
TOR Top of ramp indication.
Event Indication of selected event(s), see relay K4.
Press
Store
to save/activate the selected function.
Fieldbus
To set parameters related to the fieldbus communication, enter the Fieldbus group.
Fieldbus control (Fieldb Ctrl)
Activate the fieldbus control by changing to
Yes
.
Press
Store
to save the selected function.
Fieldbus type (Fieldb Type)
Select what fieldbus type is used.
AS-Interface Used for AS-I protocol.
Other Used for protocols other than AS-I (i.e., DeviceNet, Profibus DP, Modbus).
Press
Store
to save/activate the selected function.
Fieldbus address (Fieldb Addr)
Set a unique address number between 1 and 1000 for fieldbus communication.
Press
Store
to save the selected function.
!
Caution!
The motor may start unexpectedly if there is a start signal present when doing any of the
actions listed below:
• Switching from one type of controol to another (fieldbus control/hardwire control)
• Re-programming the programmable inputs.
• Reset all Settings (programmable input set to Enable)
Chapter 7
Settings and configuration