background image

7:1.1  Overview of all accessible settings (different menus) cont.

Description

Display

text

Setting

range

Default

value

Actual

setting

Setting current

Setting Ie

9.0...1207A

Individual

Time for start ramp

Start Ramp

1...30s, 1...120s

10s

Time for stop ramp

Stop Ramp

0...30s, 0...120s

0s

Initial voltage for start ramp

Init Volt

30...70%

30%

End voltage for stop ramp

End Volt

30...70%

30%

Step down voltage

Step down

30...100%

100%

Level of the current limit

Current Lim

2.0...7.0xle

4.0xle

Selection of kick start

Kick Start

Yes, No

No

Level of kick start

Kick Level

50...100%

50%

Time for kick start

Kick Time

0.1...1.5s

0.2s

Range for start ramp

Start Range

1-30s, 1-120s

1-30s

Range for stop ramp

Stop Range

0-30s, 0-120s

0-30s

Overload protection

Overload

No, Normal, Dual

Normal

Overload class

OL Class

10A, 10, 20, 30

10

Overload class, Dual type, Start class

OL Class S

10A, 10, 20, 30

10

Overload class, Dual type, Run class

OL Class R

10A, 10, 20, 30

10

Type of operation for overload protection

OL Op

Stop-M, Stop-A, Ind

Stop-M

Locked rotor protection

Locked Rotor

Yes, No

No

Trip level for locked rotor protection

Lock R Lev

0.5...8.0xle

4.0xle

Trip time for locked rotor protection

Lock R Time

0.2...10s

1.0s

Type of operation for locked rotor protection

Lock R Op

Stop-M, Stop-A, Ind

Stop-M

Underload protection

Underload

Yes, No

No

Trip level for underload protection

Underl Lev

0.4...0.8xle

0.5xle

Trip time for underload protection

Underl Time

1...30s

10s

Type of operation for underload protection

Underl Op

Stop-M, Stop-A, Ind

Stop-M

Phase imbalance protection

Phase Imb

Yes, No

No

Trip level for phase imbalance protection

Ph Imb Lev

10...80%

80%

Type of operation for imbalance protection

Ph Imb Op

Stop-M, Stop-A, Ind

Stop-M

High current protection

High I

Yes, No

No

Type of operation for high current protection

High I Op

Stop-M, Stop-A, Ind

Stop-M

Phase reversal protection

Phase Rev

Yes, No

No

Type of operation for phase reversal protection

Ph Rev Op

Stop-M, Stop-A, Ind

Stop-M

PTC protection

PTC

Yes, No

No

Type of operation for PTC protection

PTC Op

Stop-M, Stop-A, Ind

Stop-M

Use of external by-pass contactor

Ext ByPass

Yes, No

No

Type of operation, by-pass doesn’t open

BP Closed Op

Stop-M, Stop A

Stop-M

Type of operation, by-pass doesn’t close

BP Open Op

Stop-M, Stop A

Stop-M

High current warning

Warn I=High

Yes, No

No

Trip level for high current warning

Wa I=H Lev

0.5...5.0xle

1.2xle

Low current warning

Warn I=Low

Yes, No

No

Trip level for low current warning

Wa I=L Lev

0.4...1.0xle

0.8xle

Motor overload warning

Warn OL

Yes, No

No

Trip level for motor overload warning

Wa OL Lev

40...99%

90%

Thyristor overload warning

Warn SCR OL 

Yes, No

No

Type of operation for phase loss fault

Ph Loss Op

Stop-M, Stop-A

Stop-M

Type of operation for fieldbus fault

FB Fault Op

Stop-M, Stop-A

Stop-M

Type of operation for frequency fault

Freq F Op

Stop-M, Stop-A

Stop-M

Type of operation for heatsink overtemp fault

HS Temp Op

Stop-M, Stop-A

Stop-M

Type of operation for shorted thyristor fault

SCR SC Op

Stop-M, Stop-A

Stop-M

Function of programmable input In0

In0

None, Reset,

Enable Jog, DOL, 

Start 2, FB-Dis

Reset

Chapter 7

Settings and configuration

Low Voltage Products & Systems 

7.5

ABB nc. • 888-385-1221 • www.abb-control.com 

1SXU 132 021 M0201

7

Summary of Contents for PST30

Page 1: ...Installation and Maintenance manual Softstarters PST PSTB...

Page 2: ...nstallation and maintenance manual 12 Diagrams 12 1 12 5 11 Troubleshooting 11 1 11 6 10 Functions 10 1 10 19 9 Maintenance 9 1 9 2 8 Fieldbus communication option 8 1 8 2 7 Settings and configuration...

Page 3: ...between the softstarter and the information in this manual Author s address Low Voltage Products and Systems ABB Inc 1206 Hatton Road Wichita Falls TX 76302 Tel 888 385 1221 940 397 7000 Fax 940 397 7...

Page 4: ...1 2 Intended audience 1 2 General 1 2 Requirements 1 2 Chapters included 1 2 Revision notes 1 3 Acronyms and abbreviations 1 3 Installation and maintenance manual PST30 PSTB1050 Low Voltage Products S...

Page 5: ...ftstarter must have a basic knowledge in handling electric equipment The commissioning and maintenance per sonnel must be well experienced in using this kind of equipment 1 2 2 Chapters included Intro...

Page 6: ...n this manual Acronym abbreviation Description LED Light Emitting Diode LCD Liquid Crystal Display SCR Silicon Controlled Rectifier IT Information Technology HMI Human Machine Interface FBP Fieldbuspl...

Page 7: ...2 2 Configuration 2 3 Start of the motor 2 3 Installation and maintenance manual PST30 PSTB1050 Low Voltage Products Systems 2 1 ABB Inc 888 385 1221 www abb control com 1SXU 132 021 M0201 Chapter 2 Q...

Page 8: ...nect the functional ground terminal 3 Information The wire shall be as short as possible and be connected to the mounting plate The mounting plate should also be grounded 6 Connect the start stop circ...

Page 9: ...vigation keys PST30 300 only See Figure 11 9 Press Store and Next to continue or Back to previous parameter using the selection keys See Figure 12 10 Select Yes if ready or Tune Set if ramp times init...

Page 10: ...echnical data 3 5 General 3 5 Semi conductor fuses 3 5 Softstarter types 3 6 Weights 3 7 PSTB AC3 Across the line Contactor Ratings 3 7 UL Information 3 7 Dimensions 3 8 3 10 Installation and maintena...

Page 11: ...n interface Remote keypad option The integrated fans for cooling are operated only during ramping start stop and when the tem perature of the heat sink is too high The temperature is monitored by a th...

Page 12: ...T2 6T3 B1 B2 B3 3L2 5L3 LISTED IND CONT EQ 7F39 IEC 947 4 2 Us 100 250V AC DC Ue 220 230 380 400 500 V 72 AC 53a 8 1 6 80 6 In line 18 5 37 45 kW LIS TED 7F3 9 IND CO NT EQ Ie 37 7 2A Us 100 250V AC D...

Page 13: ...hout the product s life cycle The PST softstarters is an Industrial IT enabled product Documentation such as brochures catalogues certificates and drawings can be found at www abb control com products...

Page 14: ...se for control circuit 6A Delayed MCB use C characteristics Service factor 115 100 for PSTB1050 Communication protocols AS Interface DeviceNet Profibus DP Modbus Chapter 3 Description 3 8 2 Semi condu...

Page 15: ...350 Motor rating 380 415V KW 75 132 90 160 110 184 132 220 AC 3 Rating with integrated Bypass A Power loss at rated current W 435 540 645 765 Control power requirements VA 10 15 15 15 Type PST300 PST...

Page 16: ...600 AC3 Rating A 302 302 480 590 720 720 3 8 6 UL information Equipment suitable for use in a circuit with maximum available fault current as shown when protected by devices indicated Model Rating kA...

Page 17: ...ions PST30 72 Figure 2 Dimensions PST85 142 3 8 7 Dimensions PST30 72 Chapter 3 Description PST85 142 Inches Millimeters 3 8 Low Voltage Products Systems 1SXU 132 021 M0201 ABB Inc 888 385 1221 www ab...

Page 18: ...mensions PST175 300 Figure 4 Dimensions PSTB370 470 Inches Millimeters PSTB175 300 Chapter 3 Description PSTB370 470 Low Voltage Products Systems 3 9 ABB Inc 888 385 1221 www abb control com 1SXU 132...

Page 19: ...Figure 5 Dimensions PSTB570 1050 Inches Millimeters PSTB570 1050 Chapter 3 Description 3 10 Low Voltage Products Systems 1SXU 132 021 M0201 ABB Inc 888 385 1221 www abb control com 3...

Page 20: ...2 Handling when mounting 4 2 Requirements 4 2 Minimum distance to wall front 4 2 Minimum enclosure sizes 4 3 Installation and maintenance manual PST30 PSTB1050 Low Voltage Products Systems 4 1 ABB Inc...

Page 21: ...s lifting equipment is recommended due to the weight See Chapter 3 Description for weights Warning Do not lift the softstarter by the connection bars Lifting by the connection bars may cause damage to...

Page 22: ...losure dimensions Fan capacity W H D mm in mm in mm in m3 h ft3 min PST30 72 300 12 400 16 250 10 42 25 PST85 300 400 16 500 20 300 12 95 60 PST175 300 500 20 600 24 300 12 210 125 PSTB370 470 600 24...

Page 23: ...le output relay K4 terminals 12 13 and 14 5 6 Programmable output relay K5 terminals 15 16 and 17 5 7 Programmable output relay K6 terminals 18 19 and 20 5 7 PTC input 5 7 Connection of communication...

Page 24: ...250V Stop Start In0 In1 Vc 50 60 Hz 2 3 4 5 6 7 8 9 10 Vp Vp 11 K4 12 13 14 Vn 15 16 K5 17 18 19 K6 20 LIS TE D 7F 39 IND CO NT EQ 1S FA 89 4 00 7 IEC 94 7 4 2 Ie 37 72 A Us 10 0 2 50 V AC DC UL Uc 1...

Page 25: ...operate machine with the grounding wire disconnected 1 100 250V Stop Start In0 In1 Vc 50 60 Hz 2 3 4 5 6 7 8 9 10 Vp Vp 11 K4 12 13 14 Vn 15 16 K5 17 18 19 K6 20 B1 B2 B3 Figure 4 External bypass cont...

Page 26: ...9 10 11 Internal control voltage The softstarter has a built in holding circuit which does not require any external power source for start and stop See Figure 10 A conventional circuit with a HOA swit...

Page 27: ...momentary start signal required Chapter 5 Connection 5 2 2 4 Programmable inputs terminals 6 and 7 The softstarter has two programmable inputs In0 default reset event In1 default reset event See Chap...

Page 28: ...4 2 5 mm AWG 12 22 0 14 2 5 mm 2 2 5 2 2 5 Programmable output relay K4 terminals 12 13 and 14 The output relay gives a signal depending on the selected function Default Run See Chapter 7 Settings and...

Page 29: ...le output relay K5 terminals 15 16 and 17 The output relay gives a signal depending on the selected function Default Top of ramp See Chapter 7 Settings and configuration for programming Connect the ca...

Page 30: ...oning temporarily handheld Note that NEMA 4 4X cannot be achieved when the keypad is not mounted When thee external keypad is used both keypads will work in parallel but the softstarter keypad always...

Page 31: ...n1 Vc AC DC 50 60 Hz 2 3 4 5 6 7 8 9 10 Vp Vp 11 K4 12 13 14 Vn 15 16 K5 17 18 19 K6 20 LISTE D 7F39 IND CONT EQ 1SF A 894 007 IEC 947 4 2 Ie 37 72A Us 100 25 0V AC DC UL Uc 100 25 0V AC DC FLA 37 68A...

Page 32: ...op level 6 4 Settings menu 6 5 Local Control menu 6 5 Start Stop the motor 6 6 Jog 6 6 DOL start 6 6 Event Log menu 6 7 Status Information menu 6 7 Reset Events menu 6 7 Installation and maintenance m...

Page 33: ...well as a short explanation and the path to it in Chapter 10 Functions Path in menu Menu SETTINGS Functional Settings Start Stop Setting Ie 2 The top level of the softstarter start menu looks as in Fi...

Page 34: ...and contact your local ABB sales office 6 1 4 Locking unlocking the keypad 1 Press the upper navigation key twice to enter the parameter Keypad is Figure 16 The keypad is unlocked if the display indi...

Page 35: ...vel Settings Local Control Event Log Status Information Reset Events Figure 19 Top level 6 2 2 Top Level Top Level contains general softstarter information and the menus can be reached from here Use t...

Page 36: ...navigation keys to view different types of local control Information The LOCAL CONTROL menu can not be entered if Sequence start is selected Once the motor has been started in this menu it must first...

Page 37: ...u Figure 24 Select DOL start to close the integrated by pass contactor Select Stop to open the contactor Warning The rated motor current must never exceed the AC 3 rating of the integrated by pass con...

Page 38: ...hase current L2 Phase L3 Phase current L3 Run time Total run time of the motor No of Starts Run counter SW Ver CU Software version CU SW Ver FU Software version FU SW Ver KP 1 Software version Externa...

Page 39: ...4 Faults 7 14 7 15 Inputs 7 16 Outputs 7 17 Sequence start 7 18 7 19 Presentation Settings 7 20 Service Settings 7 21 All Settings 7 21 Changed Settings 7 21 Reset all Settings 7 22 Operation test mod...

Page 40: ...rt All default parameters are stored in the unit in case a full reset to default values is required When the fieldbus communication is selected most parameters can also be modified from this interface...

Page 41: ...n level X X Locked rotor protection time X X Locked rotor protection operation X X Underload protection X X Underload protection level X X Underload protection time X X Underload protection operation...

Page 42: ...Programmable software output V7 X X Event for relay K4 X X Event for relay K5 X X Event for relay K6 X X Event for SW output V7 X X Fieldbus control X X Fieldbus type X X Fieldbus address X X No of se...

Page 43: ...M Phase imbalance protection Phase Imb Yes No No Trip level for phase imbalance protection Ph Imb Lev 10 80 80 Type of operation for imbalance protection Ph Imb Op Stop M Stop A Ind Stop M High curre...

Page 44: ...K5 Lock Rot Yes No No Underload event of relay K5 K5 Underload Yes No No Phase imbalance event of relay K5 K5 Phase Imb Yes No No PTC event of relay K5 K5 PTC Yes No No Phase reversal event of relay K...

Page 45: ...0 7 0xle 4 0xle 1st sequence setting current 1st Set le 9 0 1207A Individual 2nd sequence time for start ramp Start Ramp 2 1 30s 1 120s 10s 2nd sequence initial voltage for start ramp Init Volt 2 30 7...

Page 46: ...ave the following functions In 0100 Start signal high In 1000 Stop signal high In 0010 In0 high In 0001 In1 high Out 1000 Relay K4 activated Out 0100 Relay K5 activated Out 0010 Relay K6 activated Out...

Page 47: ...ave the selected class Confirm the selected overload class by pressing Next If the wrong overload class was selected press Back and select the correct class External By Pass contactor Ext ByPass If an...

Page 48: ...ve the data after setting the current External By Pass contactor Ext ByPass Set the parameter to Yes if an External By pass Contactor is used otherwise select No Start ramp Set the ramp time for start...

Page 49: ...level Kick time Start range Stop range To set parameters from Setting Ie to Current limit level see Basic Settings Kick Start Activate the Kick Start function by entering this menu Press Store to save...

Page 50: ...Press Store to save the selected class Overload run class OL Class R Select the required overload class during continuous run The following overload classes are available 10A 10 20 30 Press Store to...

Page 51: ...Activate the high current protection if required by changing to Yes If Yes is selected the following setting will be available High current type of operation High I Op Select what operation should be...

Page 52: ...re to save the selected operation Warning SCR overload Warn SCR OL Activate the warning function if required by changing to Yes Press Store to save the selected operation 7 2 4 4 Faults Phase loss typ...

Page 53: ...d Press Store to save the selected operation By pass doesn t open operation Select what operation should be asserted if the contactor does not open Stop M The motor will stop and a manual reset is req...

Page 54: ...s Reset all Settings programmable input set to Enable Second programmable input In1 Select the required function for the input In1 One of the following functions can be selected None No specific funct...

Page 55: ...tore to save activate the selected function SW Outp V7 Select the required function for the fieldbus communication output SW Outp V7 One of the following functions can be selected Run Run indication T...

Page 56: ...ill only be displayed if parameter No of Seq is set to 2 or 3 Information If sequence start was used and the parameter No of Seq is changed to No the overload protection will automatically be set to N...

Page 57: ...rs can be adjusted 2nd Set Ie Setting current Start Ramp2 Ramp time for start Init Volt2 Initial voltage Curr Lim2 Current limit Press Store to save the selected parameter Third sequence parameters 3r...

Page 58: ...ouch any of the keys to turn it on again Date Type The date can be presented in three different ways Depending on the selected type the following will be displayed at the top level Date type Display o...

Page 59: ...in contrast to the factory default setting If no parameters have been changed the LCD will display No Changed Settings Figure 33 Service Settings menu for authorized personnel only Top level Settings...

Page 60: ...e unit is put into operation As long as the unit is in demo mode the color on the display is inverted except on the external keypad Caution Never enter the demo mode with the main voltage connected Th...

Page 61: ...d Settings The Changed settings menu consists of all parameters that have been changed from the factory default setting If no parameters have been changed the LCD will display No Changed Settings 7 2...

Page 62: ...ntenance manual PST30 PSTB1050 Overview 8 2 Required accessories 8 2 Instructions 8 2 Low Voltage Products Systems 8 1 ABB Inc 888 385 1221 www abb control com 1SXU 132 021 M0201 Chapter 8 Fieldbus co...

Page 63: ...oftstarter to a fieldbus system the following accessories are required Fieldbusplug for appropriate protocol check that the cable length is sufficient Connectors for bus connection End plug some proto...

Page 64: ...ation and maintenance manual PST30 PSTB1050 Regular maintenance 9 2 Service and repair 9 2 Low Voltage Products Systems 9 1 ABB Inc 888 385 1221 www abb control com 1SXU 132 021 M0201 Chapter 9 Mainte...

Page 65: ...oling airways are free from dirt and dust If required use pressurised air to clean Check external filters Clean if necessary Check that the fan is working and rotating freely The blades should rotate...

Page 66: ...7 Underload protection 10 8 Underload protection level 10 8 Underload protection time 10 8 Underload protection type of operation 10 8 Phase imbalance protection 10 8 Phase imbalance protection level...

Page 67: ...16 Current limit first sequence 10 16 Setting current first sequence 10 16 Start ramp second sequence 10 16 Initial voltage second sequence 10 16 Current limit second sequence 10 17 Setting current s...

Page 68: ...Menu SETTINGS Functional Settings Start Stop Start Ramp When a start signal is given the softstarter performs a start ramp by gradually increasing the output voltage to the motor The start ramp contin...

Page 69: ...achieved It is mainly used for pump applications Parameter text Default value Setting range Description Step down 100 30 100 Voltage value to which the softstarter will step down at stop and where it...

Page 70: ...ssible to set the time of the kick start It is active only if kick start is selected Parameter text Default value Setting range Description Kick Time 0 2s 0 1 1 5s Time for Kick Start 10 11 Start ramp...

Page 71: ...20 Class 30 Parameter text Default value Setting range Description OL Class 10 10A 10 20 30 Overload class 10 15 Overload class dual type start class Path in menu Menu SETTINGS Functional Settings Pro...

Page 72: ...to set the level of the locked rotor protection It is active only if Locked rotor protection is selected Parameter text Default value Setting range Description Lock R Lev 4 0 x Ie 0 5 8 1 xle Trip le...

Page 73: ...t is active only if underload protection is selected Parameter text Default value Setting range Description Underl Time 10s 1 30s Trip time for Underload protection 10 25 Underload protection type of...

Page 74: ...a current protection with a fixed level of 8 x Ie during 200 ms The protection is activated if the current exceeds this level and time Parameter text Default value Setting range Description High I No...

Page 75: ...ns PTC PTC Op This parameter makes it possible to select between three different actions when the protec tion is activated It is active only if the PTC protection is selected Stop M The motor stops an...

Page 76: ...L Lev 0 8 x Ie 0 4 1 0 x Ie Trip level for low current warning 10 40 Overload warning Path in menu Menu SETTINGS Functional Settings Warnings Warn OL If the function is selected a warning signal will...

Page 77: ...f operation for fieldbus fault 10 45 Frequency fault type of operation Path in menu Menu SETTINGS Functional Settings Faults Freq F Op This parameter makes it possible to select between two different...

Page 78: ...grammable inputs In0 and In1 They can be used for different purposes depending on the selected function independently of each other Parameter text Default value Setting range Description In0 Reset Non...

Page 79: ...ction Phase Imbalance Protection PTC Protection Description Fault group consists of By pass contactor does not close Phase loss fault Fieldbus fault Frequency fault Heat sink temp fault Shunt fault gr...

Page 80: ...lt value Setting range Description Fieldb type Other AS Int Other Type of fieldbus AS Interface short protocol Other long protocol 10 53 Fieldbus address Path in menu Menu SETTINGS Functional Settings...

Page 81: ...Ie 2 0 7 0xle First sequence current limit 10 58 Setting current first sequence Path in menu Menu SETTINGS Functional Settings Seq Start 1st Seq Param 1st Set Ie This parameter makes it possible to se...

Page 82: ...s Third sequence time for start ramp 10 64 Initial voltage third sequence Path in menu Menu SETTINGS Functional Settings Seq Start 3rd Seq Param Init Volt3 This parameter makes it possible to set the...

Page 83: ...ay auto matic turn off 10 69 Password Path in menu Top level Press Upper navigation key once This parameter makes it possible to set a password to lock the keypad All menus are avail able when the key...

Page 84: ...sed Op Path in menu Menu SETTINGS Functional Settings Faults BP Closed Op This parameter makes it possible to select between two different actions of the softstarter if the by pass contactor does not...

Page 85: ...verview of indications 11 2 General problems and faults 11 2 Start up faults 11 3 Fault indication 11 3 11 4 Protection indication 11 5 11 6 Low Voltage Products Systems 11 1 ABB Inc 888 385 1221 www...

Page 86: ...ut given start signal Shorted SCR By pass contactor stuck in the closed position Check and replace Check and correct the reason Bad motor sound during start and operation Inside Delta connection wrong...

Page 87: ...lta connected Check that there are no connections missing to the motor Check that the circuits are closed and correspond to the circuit diagram Check and replace Frequency fault Power on Protection Fa...

Page 88: ...SCR fault Power on Protection Fault Fault Open SCR Reset Back One or several SCRs are not conducting Check and replace Contact your ABB sales office for replacement parts Fieldbus fault Power on Prot...

Page 89: ...ion Power on Protection Fault Prot Underload Reset Back The motor current is below set level and time Check and correct the reason for the underload Check that the settings are according to the operat...

Page 90: ...otection Fault Prot SCR OL Reset Back The softstarter is too small Too many starts hour The ramp time for start is too long Check and replace the softstarters with one of a suitable size Check and dec...

Page 91: ...T30 PST300 12 2 Circuit Inside Delta diagram PST30 PST300 12 3 Circuit Inline diagram PSTB370 PSTB1050 12 4 Circuit Inside Delta diagram PSTB370 PSTB1050 12 5 Low Voltage Products Systems 12 1 ABB Inc...

Page 92: ...ST300 Figure 1 Circuit diagram PST30 3000 Terminal 3 is a functional ground it is not a protective ground It shall be connected to the mounting plate 12 2 Low Voltage Products Systems 1SXU 132 021 M02...

Page 93: ...Terminal 3 is a functional ground it is not a protective ground It shall be connected to the mounting plate IGH VOLTAGE 12 2 Circuit Inside Delta PST30 PST300 Low Voltage Products Systems 12 3 ABB Inc...

Page 94: ...1050 Figure 3 Circuit diagram PSTB370 PSTB1050 Terminal 3 is a functional ground it is not a protective ground It shall be connected to the mounting plate 12 4 Low Voltage Products Systems 1SXU 132 02...

Page 95: ...LTAGE Chapter 12 Diagrams 12 4 Circuit Inside Delta PSTB370 PSTB1050 Figure 4 Circuit diagram PSTB370 PSTB1050 Low Voltage Products Systems 12 5 ABB Inc 888 385 1221 www abb control com 1SXU 132 021 M...

Reviews: