Chapter 10
Functions
10:37 High current warning level
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn I=High/Wa I=H Lev
This parameter makes it possible to set the indication level of the high current warning function.
Parameter text
Default value
Setting range
Description
WA I=H Lev
1.2 x Ie
0.5...5.0 x Ie
Trip level for high cur-
rent warning
10:38 Low current warning
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn I=Low
If the function is selected, a warning signal will be given provided that the current during full
voltage is lower than the set value. The measurement starts 30 seconds after
full voltage
is reached.
Parameter text
Default value
Setting range
Description
WA I=Low
No
Yes, No
Low current warning
10:39 Low current warning level
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn I=Low/Wa I=L Lev
This parameter makes it possible to set the indication level of the low current warning function.
Parameter text
Default value
Setting range
Description
WA I=L Lev
0.8 x Ie
0.4...1.0 x Ie
Trip level for low
current warning
10:40 Overload warning
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn OL
If the function is selected, a warning signal will be given that the overload protection will be
activated if the motor load does not decrease.
Parameter text
Default value
Setting range
Description
Warn OL
No
Yes, No
Overload warning
10:41 Overload warning level
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn OL/Wa OL Lev
This parameter makes it possible to set the indication level of the motor overload protection.
The actual trip level of the protection is represented by 100%.
Parameter text
Default value
Setting range
Description
Wa OL Lev
90%
40...99%
Trip level for overload
warning
10:42 SCR overload warning
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn SCR OL
If this function is selected, a warning signal will be given that the SCR overload protection
will be activated if the current does not decrease. The warning level is 90%.
Parameter text
Default value
Setting range
Description
Warn SCR OL
No
Yes, No
SCR overload warning
Low Voltage Products & Systems
10.11
ABB Inc. • 888-385-1221 • www.abb-control.com
1SXU 132 021 M0201
10