ELECTRICAL INSTALLATION
PRODUCT
PCS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS600000 E40
REV.
G
LANG.
en
PAGE
6.7.3. Converter grounding
The PE conductor for the cabinet is connected to chassis potential at the base frame as
shown in Fig. 6–10.
The shields of the power cables are connected to the grounding bars close to the phase
connectors as shown in Fig. 6–11.
External grounding cables must be connected from the main ground (PE) of the installation
to the converter.
Figure 6–10 Grounding cam at a base frame with M12 bolt
Figure 6–11 Ground rail for cable shield connections