8.6. Starting the PCS6000 converter
The PCS6000 can only be taken into operation after it has been properly installed and
commissioned.
8.6.1. Checks before starting
IMPORTANT!
Before commissioning and first start-up proceed according to chapter 7,
If the PCS6000 has been de-energized for maintenance or repair work, proceed as follows.
Pre-start checks
1.
Check that no tools, grounding equipment and other objects are left in any of the units.
2.
Check that the grid is energized.
3.
The “Anti-dew startup sequence” release for converter start.
See section 8.5,
4.
Check that the auxiliary power supply of the PCS6000 is switched on.
See “Wiring Diagrams units in Appendix A03 - Electrical drawings” for project-specific
details.
5.
Check that the water cooling system is ready for operation.
6.
Check that all unit doors are properly closed.
• All units containing live MV equipment are equipped with door switches and solenoid
coils.
• If a door is not closed, the converter start will be prevented.
• Check that the PCS6000 is ready, ie, no fault message is pending.
7.
Check that the Key Switch is in “ON” position.