![ABB PCS6000 User Manual Download Page 72](http://html1.mh-extra.com/html/abb/pcs6000/pcs6000_user-manual_3052170072.webp)
ELECTRICAL INSTALLATION
PRODUCT
PCS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS600000 E40
REV.
G
LANG.
en
PAGE
72/114
6.4.3. Generator side (converter - generator)
6.4.4. Braking resistor connection
NOTE – In some cases, the braking resistor cables are included in the converter delivery.
Topic
Value
Unit
Comment
Number of phases
1 × 3 (1CL)
2 × 3 (2CL)
Connection
Pfisterer P3PS panel socket
Number of connections
2 or 3 / phase
Plugs for up to two cables can be
connected. For more information,
see the project
-
specific
documentation.
du/dt
< 2.5
kV
At converter terminals
Rated voltage
3300
V
Insulation U
0
/ U
6 / 10
kV
IEEE: 5 / 8 kV
Rating factor
0.85
-
To cover converter operation
Maximum length
100
m
Single phase current
3
kArms
Maximum 3 s
Topic
Value
Unit
Comment
Number of phases
2 per resistor
2 resistors per BRU
Connection
Pfisterer P3PS panel socket or
cable glands
Rated fundamental voltage
2.8
kV
Insulation U
0
/ U
6 / 10
kV
IEEE: 5 / 8 kV
Rating factor
0.85
-
To cover converter operation
Maximum length
6
m