114
PCS100 UPS-I
User Manual
—
12
REMOTE MONITORING
The PCS100 UPS-I provides remote access for monitoring purposes. Following monitoring connections are
available:
–
Integrated Web server. Using the integrated web server, the same information as displayed on the
GDM is available on any networked PC connected to the PCS100 UPS-I. In addition, downloading
event and service information is possible from the integrated web server.
–
Modbus TCP. For connection to plant wide SCADA or monitoring systems the PCS100 UPS-I has a list
of registers that can be accessed.
–
Email Connectivity. An email notification service can be set up to send notifications of power quality
and system events
Communication Type
Description
Port
Connection
Remote Web Pages
Webserver via HTTP, Ethernet
80
Standard RJ45
SW upgrade via SSH
22
Standard RJ45
Monitoring system
Modbus TCP
502
Standard RJ45
Remote notifications
Standard RJ45
Remote Web Pages
Remote Web Pages are a set of web pages that are
similar in format to the standard GDM and accessed
through the integrated web server via the GDM Ethernet
connection. Through this interface the users can
remotely access the status and operating parameters.
Viewing and downloading of event history and service
logs is also available.
Access is via the Ethernet port of the GDM and web
pages can be viewed any standard web browser on a
device connected to the same network.
Note: for security reasons start/stop control and
parameter menus are disabled by default. However, they
can be enabled through parameter settings on the unit.
Modbus TCP
Modbus TCP connection is also provided via the Ethernet
port of the GDM user interface.
Read Only access is available to operating parameters
such as voltages, currents and power levels.
Figure 12
-
1: PCS100 UPS
-
I remote monitoring
diagram