PCS100 UPS-I
User Manual
121
Address
Name
Access
Type
Raw Value & Scaling
17
Inverter DC Bus
Voltage minimum
Read Only 16-bit,
Signed
Voltage (Volts) = 480 * 0.816496 * Raw value / 8192
(Inverter module with min DC voltage)
18
Inverter DC Bus
Voltage maximum
Read Only 16-bit,
Signed
Voltage (Volts) = 480 * 0.816496 * Raw value / 8192
(Inverter module with max DC voltage)
19
Storage DC Voltage
(Same as on Status
page)
Read Only 1- bit,
Signed
Voltage (volts) = 480 * 0.816496 * Raw value / 8192
20
Active Event Code
(Same as GDM
status line)
Read Only 16-bit,
Signed
Refer to Table 11-2 for a list of event codes. Code 0
indicates there are no active events (no
warning/fault)
21
Discharge Count
Read Only 16-bit,
Signed
Discharge count = Raw value
22
Detailed Status
Read Only 16-bit,
Signed
0
–
System is initializing (Startup web page)
1
–
Fault
2 - Clearing Fault
3 - Static Bypass
4 - Starting
5 - On Line
20
–
Inverter Not ready (Starting - System Bypass
state shown in the Figure 7-6 (state flow diagram))
21
–
Discharging
22
–
Discharging (Wait for stable mains)
23
–
Discharging (Synchronizing)
24
–
Online
25
–
Mains Lost while returning to mains.
26
–
Discharge T/O
27
–
Storage Empty
28
–
Inverter Off (problem with inverter. FSB
closed)
29
–
Discharge Overload
30
–
Test_Mode (UD Open test (menu 612) - refer to
Figure 7-6)
31
–
Walking in (28 Transfer Back - refer to Figure
23
Read Test
Read Only 16 bit
unsigned
Counts up by one for each access to this register.
Can be used by Modbus masters to check
connection.
100 &101 Date and Time
(To read & set the
date and time)
Read/Writ
e
32bit
Unsigned
Unit is seconds.
Datum is 00:00:00 1/1/1970.
e.g.: 1297296764 is 00:12:31 10/2/2011
102
Read/Write Test
Read/Writ
e
16 bits
Register for use by customer for testing Modbus.
Not used by PCS100 UPS-I
Table 12
-
2: PCS100 UPS
-
I Modbus TCP user parameters
Address Name
Access
Type
Raw Value & Scaling
1001-
1023
Cached registers 1-
23 (see section
Error! Reference
source not found.
)
Read Only As for
registers
1-23
Same as for registers 1-23
Table 12
-
3: PCS100 UPS
-
I Modbus TCP cached user parameters