120
PCS100 UPS-I
User Manual
Address Name
Access
Type
Raw Value & Scaling
1
Product Status
Read Only 16-bit,
Enum
0
–
FAULT
1
–
STOP
2
–
STARTING
3
–
RUN
4
–
STOPPING
5 - BYPASS
2
Warning Indication
(same as warning
relay)
Read Only 16-bit,
Enum
0
–
NOT WARNING
1
–
WARNING
3
Inhibit Indication
(same as inhibit
switch)
Read Only 16-bit,
Enum
0
–
NOT INHIBIT
1
–
INHIBIT
4
Supply Voltage
(same as parameter
121)
Read Only 16-bit,
Signed
Voltage (line-to-line RMS Volts) = Raw value
e.g., Raw value = 480
Voltage = 480 V
5
Supply Frequency
(same as parameter
122)
Read Only 16-bit,
Signed
f (Hz) = Raw value / 32
e.g., If the Raw value = 1920 the frequency = 60 Hz
6
System Current
(Same as parameter
112)
Read Only 16-bit,
Signed
Current (RMS Amperes) = Raw value
e.g., Raw value = 500
Current = 500 A
7
Input Voltage V1-V2 Read Only 16-bit,
Signed
Voltage (line-to-line RMS Volts)
= Raw value x Sys base voltage / 8192
e.g., Raw value = 7782
Sys base voltage = 480V (parameter 121)
Voltage (line-to-line RMS) = 456 V
Voltage (% of rated voltage)
= Raw value x 100 / 8192
e.g., Raw value = 8192
Voltage = 100%
8
Input Voltage V2-V3 Read Only 16-bit,
Signed
9
Input Voltage V3-V1 Read Only 16-bit,
Signed
10
Output Voltage V1-
V2
Read Only 16-bit,
Signed
11
Output Voltage V2-
V3
Read Only 16-bit,
Signed
12
Output Voltage V3-
V1
Read Only 16-bit,
Signed
13
Load Current I1
Read Only 16-bit,
Signed
Phase Current (RMS Amperes)
= Raw value x rated current / 8192
e.g., Raw value = 5792
rated current = 500 A (parameter 112)
Current = 354 A
Current (% of rated current)
= Raw value x 100 / 8192
e.g., Raw value = 4096
Current = 50%
14
Load Current I2
Read Only 16-bit,
Signed
15
Load Current I3
Read Only 16-bit,
Signed
16
Frequency
Read Only 16-bit,
Signed
Frequency (Hz)
= Raw value x Rated frequency / 8192
e.g., Raw value = 8192
Rated frequency = 60 Hz
Frequency = 60.0 Hz