110
PCS100 UPS-I
User Manual
Code Origin Event
Type
GDM Description Event Description
Recommended Action
221
S
W
Bypass not ready
Three things can produce this
warning:
1.
The FSB spring is discharged.
2.
There is an under voltage on the
FSB Interface Board. LED 3 will turn
off while the under voltage is
present and the Interface Board will
autonomously close the FSB. The
master will detect the un-
commanded closure via the FSB
aux contacts and will trigger event
325.
3.
The SOR test device in the FSB
enclosure has detected the ACB
close coil resistance is out of
tolerance.
When this warning is present LED
5 on the utility disconnect
interface board (see Table 7-11)
and LED 7 on the SCR firing board
will be off (not illuminated). The
FSB will close while this Warning is
present even if the PCS100 UPS-I
is ON LINE. This warning is
masked for the first 6 seconds it
is active to allow time for the FSB
spring to charge.
(1) View the window on the
front of the ACB to see if the
operating spring is charged.
(2) View the FSB Interface
PCB LED3 (ULVO). If it is off
the PCB has detected a low
DC voltage supply and has
commanded the ACB to
close. Check the LVDC
power supply to the FSB
interface board is above the
threshold (23Vdc)
(3) View the Fault LED on the
SOR test unit.
222
S
Info
Discharge -
transient
The utility’s transient voltage
threshold has been breached and
the PCS100 UPS-I has:
(1) begun supplying the load from
the PCS100 UPS-
I’s Energy
Storage and
(2) disconnected the load from
the utility.
Info only
223
S
Info
Discharge - test
A test discharge has been
performed using parameter 622
Test Activate.
Info only
225
S
Info
Module Charger
The Module Charger has changed
state (on/off).
Info only
283
I
F
Many contactor
activations
The Inverter pre-charge contactor
is switching too often.
Check Event Log for
primary cause.
285 I
F
Sequence
Mismatch Error
A module has detected that its
phase sequence differs from the
Auxiliary Master Module.
Check grid voltage phase
rotation is correct and
check voltage sensing
wiring.
307 S
Info
Discharge -
frequency
The utility frequency has
breached its threshold and the
PCS100 UPS-I has:
(1) begun supplying the load from
the PCS100 UPS-I Energy Storage
Info only