Quick Start Guide
Alarm Reset
Information: Clear Breaker Alarm
The Alarm Card monitors all breakers that were once ON.
Breaker Alarms occur while breakers are OFF or TRIPPED.
Clear Breaker Alarm
Turn the breaker ON
or
Press the Alarm Reset button to ignore all breakers that are OFF or TRIPPED, until they
Information: Rectifier Options
Rectifier
Input
Output 48Vdc
Recommended 3
-
phase AC Breaker (PH
-
N)
“
WYE
”
1
-
shelf
(3 rectifiers)
AC Breaker/Wire Gauge
1
-
shelf
(3 rectifiers)
AC Breaker/Wire Gauge
Eco Rectifier
blue
NE050ECO48ATEZ
ac 200
-
277 Vac
50A
20A /12 AWG
40A / 8 AWG
Rectifier
blue
NE075AC48ATEZ
ac 200
-
277 Vac
75A
30A / 10 AWG
50A / 8 AWG
NE050AC48ATEZ
ac 208
-
277 Vac
50A
20A / 12 AWG
40A / 8 AWG
Surge Protectors
Force During insert to
module to the base
Information: Surge Protectors
Surge Protection Device consists of three RU
-
320
-
25 field
-
replaceable modules protecting Line to Neutral and
one RU
-
180
-
25 field
-
replaceable module protecting Neutral to Ground. See page11 for ordering replacement
module information.
Replace pluggable modules if RED indicator tab is visible on any of the multiple pole units. To remove:
1.
Verify that you have the correct replacement module.
2.
Disconnect power.
3.
Pull the pluggable module from the base.
4.
Push a new pluggable module into the base. You will hear a
“
click
”,
indicating that the module is set in place. An
insertion
“
key
”
built into the unit will help ensure that the module has been correctly selected.
CAUTION : Use of
excessive ion, can
result in damage
L1
L2
L3
Red Indicator
Window
N