Page 7
© 2021 ABB. All rights reserved.
Quick Start Guide
Step 11
-
Configure Controller
(continued)
Alarm Relay Jumpers and 1
-
Wire Data reference
Jumpers are located on the top of the controller.
Alarm Relay Jumper Factory Defaults are Open On Alarm
1
-
Wire Reference Factory Default is
-
48V.
Step 12
-
Controller Basic Operation
Controller Alarm Status: The display changes colors; Green = Normal, Amber = Minor Alarm, Red = Critical/Major
Alarm
Some alarms may occur during initial installation; example: thermal probe fail or Major/Minor communication
fail.
Clear these alarms: Via Controller Display: follow the menu path; Menu > Control/Operation > Clear Events or
Uninstall Equipment.
Via web pages or EasyView2; Select the Maintenance tab > clear latched events and clear
missing devices.
Verify Basic Installation Settings: Date, Time, Battery Type, number of strings and float voltage
Controller Display
-
Menu > Configuration > System Settings and Menu > Configuration > Batteries.
Web pages or EasyView2
-
Installation Tab for Date, Time. Site ID and Site Description
Settings Tab > Battery Management for Battery
Type and number of battery strings installed
Plant Status LEDs
LCS Display
Voltage Test Jacks
Menu Navigation
Cart port
behind door
Front Display
Front Display Menu Map
Web Home Page