Page 9
© 2021 ABB. All rights reserved.
Quick Start Guide
Information: Alarm Connection
Alarm Outputs
Alarm relays are factory set to Open On Alarm. If Close On Alarm is desired ad
-
just controller alarm jumpers. See
diagram in step 8 for the location of the con
-
troller alarm jumpers. Alarm output is a 20
-
pin latching connector.
Alarm relays
Alarm Inputs
Pin
Color
Option 2
Standard Controller Alarm
Output Defaults
Color
Option 1
PCR
Power Critical
1
BL
BL
PCR_C
Power Critical_C
11
Bl/BK
W
PMJ
Power Major
2
O
O
PMJ_C
Power Major_C
12
O/BK
W
PMN
Power Minor
3
G
G
PMN_C
Power Minor_C
13
G/BK
W
R1
Battery On Discharge
4
W
BR
R1_C
Battery On Discharge_C
(BD_C)
15
W
W/BK
R2
Very Low Voltage (VLV)
5
S
BK
R2_C
Very Low Voltage_C
(VLV_C)
15
W
BK/W
R3
Fuse Alarm Major (FAJ)
6
BL
BL/W
R3_C
Fuse Alarm Major_C
(FAJ_C)
16
R
BL/R
R4
AC Fail (ACF)
7
O
Q/R
R4_C
AC Fail_C (ACF_C)
17
R
R
R5
Rectifier Fail (RFA)
8
G
G/W
R5_C
Rectifier Fail_C (RFA_C)
18
R
R/G
R6
Mult. Rectifier Fail
(MRFA)
9
BR
W/R
R6_C
Mult. Rectifier Fail_C
(MRFA_C)
19
R
R/W
R7
High Voltage (HV)
10
S
BK/R
R7_C
High Voltage_C (HV_C)
20
R
R/BK
Standard Controller
Alarm Output Defaults
Pin
Color
Option 1
Color
Option 2
PCR
Power Critical
1
BL
BL
PCR_C
Power Critical_C
11
W
Bl/BK
PMJ
Power Major
2
O
O
PMJ_C
Power Major_C
12
W
O/BK
PMN
Power Minor
3
G
G
PMN_C
Power Minor_C
13
W
G/BK
R1
Battery On
Discharge
4
BR
W
R1_C
Battery On
Discharge_C
(BD_C)
15
W
W/BK
R2
Very Low Voltage
(VLV)
5
S
BK
R2_C
Very Low Voltage_C
(VLV_C)
15
W
BK/W
R3
Fuse Alarm Major
(FAJ)
6
BL
BL/W
R3_C
Fuse Alarm Major_C
(FAJ_C)
16
R
BL/R
R4
AC Fail (ACF)
7
O
Q/R
Alarm Output Cables
Alarm Input Cables
CC848890137
5 ft.
CC848890153
5 ft.
CC109157442
15ft
CC848865980
15ft
CC848817635
50 ft
CC848817651
50 ft
CC848817643
150 ft
CC848817668