Modbus registers
B91
Register name
Register
address
Data type
Swap mode Description
Level Sensor ID
1
3001
UINT16
ID = Modbus address, 0-247 Valid[Native Byte]
# Levels
3002
UINT16
1 or 2 Levels Valid[Native Byte]
Error Code
3003
UINT16
Single highest alarm bit value[Native 16 Int]
Warning alarms
3004
UINT16
Diagnosis Condition Details priority [0 = No Error, else =
Error/Warning with highest priority
NOTE:
the higher the number is, higher is the priority
Level 1 (top)
7001
Float32
Reg. 3000
top Liquid height from bottom (Inches)
Level 2 (Interface) 7003
Float32
Reg. 3000
Interface Liquid height from bottom (Inches)
temperature
7005
Float32
Reg. 3000
tank temperature (Deg F)
DIp Switch Status 10000
UINT16
On-Board DIp Switch Status
hMI Software
Revision
10001
UINT16
hMI Software Revision
tpROC alarm
10002
UINT16
External temperature additionnal status
1 Registers 3001, 3002, 3003, 3004, 7001, 7003 and 7005 are used to emulate an ABB LevelMaster
Summary of Contents for LWT300 series
Page 1: ... USER GUIDE LWT300 series Guided wave radar level transmitter Modbus ...
Page 36: ...Page intentionally left blank ...
Page 40: ...Page intentionally left blank ...
Page 66: ...Page intentionally left blank ...
Page 70: ...Page intentionally left blank ...
Page 76: ...Page intentionally left blank ...
Page 96: ...Page intentionally left blank ...
Page 98: ...Page intentionally left blank ...
Page 104: ...Page intentionally left blank ...
Page 105: ...Page intentionally left blank ...
Page 106: ...Page intentionally left blank ...
Page 107: ......