68
NOTICE
For instrument configuration with software tools running on a PC, you must disconnect
the LWT from the flow computer/RTU.
When you are done configuring the instrument remotely via a HART/RS-485 connection with a
PC,
you must
toggle the communication mode back to
Operation
; otherwise the instrument
will not be able to resume sending data when reconnected to the Modbus network.
Toggling via hardware
Hardware configuration is performed via dip switches, as explained below.
WARNING
All connections must be established in a de-energized state. Before working on the circuit,
secure the breaker to prevent any accidental power-up.
In an explosion proof/flameproof installation,
do not remove the covers while the
instrument is energized.
NOTICE
DIP switch settings
always
have priority over HMI settings.
1
Make sure that the instrument is powered off and that the M4 hex head locking screws are screwed
in (see Figure 49).
2
Unscrew the housing cover on the HMI side (hazardous area warnings must be heeded; see “Safety”
on page 1).
CAUTION
Do not grab the instrument by its threaded interface. Thread edges are sharp and
constitute a risk of personal injury (see Figure 20 on page 29).
3
Pull the HMI board away from the communication board. You gain access to the communication
board.
Summary of Contents for LWT300 series
Page 1: ... USER GUIDE LWT300 series Guided wave radar level transmitter Modbus ...
Page 36: ...Page intentionally left blank ...
Page 40: ...Page intentionally left blank ...
Page 66: ...Page intentionally left blank ...
Page 70: ...Page intentionally left blank ...
Page 76: ...Page intentionally left blank ...
Page 96: ...Page intentionally left blank ...
Page 98: ...Page intentionally left blank ...
Page 104: ...Page intentionally left blank ...
Page 105: ...Page intentionally left blank ...
Page 106: ...Page intentionally left blank ...
Page 107: ......