Ch a p tER 7
Setting calibration parameters
Part of your instrument measurement accuracy resides in proper calibration of the vessel empty and full
states. The values associated with these states are usually configured upon starting the instrument via
the
Easy Setup
menu. Should the configuration performed via the
Easy Setup
menu prove incorrect,
you will have to recalibrate your instrument and enter new values. This can be done in software (via
the
Calibrate
menu; see Figure 46) or by emptying and then filling the vessel whose level you want to
measure. The following pages explain how to do this.
—
Figure 45
Calibration parameters
Full/Span
Empty/Zero
Probe length
Sensor
reference
Ullage
Level
Distance
Level offset
+ sensor offset
NOTICE
Depending on the installation, sensor reference is calculated either from the bottom of
the flange or the last thread of the coupler (see zoom-in on Figure 45 above).
Summary of Contents for LWT300 series
Page 1: ... USER GUIDE LWT300 series Guided wave radar level transmitter Modbus ...
Page 36: ...Page intentionally left blank ...
Page 40: ...Page intentionally left blank ...
Page 66: ...Page intentionally left blank ...
Page 70: ...Page intentionally left blank ...
Page 76: ...Page intentionally left blank ...
Page 96: ...Page intentionally left blank ...
Page 98: ...Page intentionally left blank ...
Page 104: ...Page intentionally left blank ...
Page 105: ...Page intentionally left blank ...
Page 106: ...Page intentionally left blank ...
Page 107: ......