background image

I.L. 41-748.1F

13

7.5.

INDICATING CONTACTOR SWITCH (ICS)

No setting is required on the ICS unit except the
selection of the 0.2 or 2.0 ampere tap setting. This
selection is made by connecting the lead located in

front of the tap block to the desired setting by means
of the connecting screw. When the relay energizes a
125 volt or 250 volt dc type WL relay switch, or equiv-
alent, use the 0.2 ampere tap. For 48 volt dc applica-
tions set ICS in 2 ampere tap and use Style
#304C209G01 type WL relay coil or equivalent.

7.6.

UNDERVOLTAGE UNIT

The voltage unit is calibrated to close its contact
when the applied voltage is reduced to 53 volts. The
voltage unit can be set to close its contacts from 40
volts to 70 volts by adjusting the resistor located in
the rear, second from the bottom. The spiral spring is
not disturbed when making any setting other than the
calibrated setting of 53 volts.

7.7.

DIRECTIONAL SETTING

There is no setting to be made on directional unit.

Tabulated Settings

Z

M

L Lead

R Lead

0.87 TS
0.89 TS
0.92 TS
0.94 TS
0.97 TS

TS

1.03TS

1.06 TS

1.1 TS

1.14 TS
1.18 TS

+.15
+.12
+.09
+.06
+.03

0

+.03

-.06
-.09
-.12
-.15

Upper .06
Upper .06
Lower .06
Upper .06

.03

0
0

Lower .06

0

.03

0

0

.03

0

Lower .06

0
0

.03

Upper .06
Lower .06
Upper .06
Upper .06

Table 1:

RECOMMENDED SETTINGS FOR KLF RELAY

ZONE 1 (ALONE)

ZONE 2 (ALONE)

BOTH ZONE 1 & ZONE 2

IMPEDANCE SETTING

See Figure 11

See Figure 12

See Figure 11 & 12

VOLTAGE SETTING

(a) Contact shorted or
(b) Set at 80% for security

80%

Zone 1 voltage contact
shorted with Zone 2 set
at 80%

TD-1

1/4 to 1 sec

(1 sec preferred)

1/4 to 1 sec

(1 sec preferred)

Zone 1 timer = 1/4 sec
Zone 2 timer = 1 sec

TD-2

Not required for
(a) above. For
(b) above use 1 min.

1 min.

1 min.

ADVANTAGES

Less sensitive to
stable system swings

1) More sensitive to

LOF condition

2) Can operate on

partial LOF

3) Provide alarm features

for manual operation

(1) Same as (1), (2) and

(3) at left.

(2) Provides back-up

protection

Table 2:

SPECIAL SETTINGS FOR MULTI MACHINES BUSSED AT MACHINE TERMINALS

ZONE 1 (ALONE)

ZONE 2 (ALONE)

BOTH ZONE 1 & ZONE 2

IMPEDANCE SETTING

See Figure 11

See Figure 12

See Figure 11 & 12

VOLTAGE SETTING

(a) Contact shorted or
(b) Set at 87% for security

87%

Zone 1 voltage contact
shorted with Zone 2 set at
87%

TD-1

1/4 to 1 sec

(1 sec preferred)

1/4 to 1 sec

(1 sec preferred)

Zone 1 timer = 1/4 sec
Zone 2 timer = 1 sec

TD-2

Not required for (a) above
(a) above. For
(b) above use 10 sec for

cond. cooled, 25 sec
for conv. cooled

10 sec for cond. cooled.
25 sec for conv. cooled.

10 sec for cond. cooled
25 sec for conv. cooled

Summary of Contents for KLF-1

Page 1: ...due to inadvert ent loss of potential such as due to a blown potential fuse On circuits with 3 phase 3 wire connected volt age transformers the type KLF relay is used 2 CONSTRUCTION The relay consists...

Page 2: ...I L 41 748 1F 2 Figure 1 Type KFL 1 Relay...

Page 3: ...e the magnetic core from the frame The electromagnet has two sets of two series con nected coils mounted diametrically opposite one another to excite each set of poles Locating pins on the electromagn...

Page 4: ...is attached to the moving contact arm by a spiral spring The spring adjuster is also held in place by a spring type clamp When contacts close the electrical connection is made through the stationary...

Page 5: ...ses the moving con tacts bridge two stationary contacts completing the trip circuit Also during this operation two fingers on the armature deflect a spring located on the front of the switch which all...

Page 6: ...ly by ZC Figure 6 assumes that ZC is positive circle includes origin If the current coil link is reversed the compensation becomes ZC In figure 6 b this change would result in VPOL being reduced rathe...

Page 7: ...the range of 60 to 100 percent of normal system voltage The actual range of adjustment is 40 to 70 VL N The dropout ratio of the unit is 98 percent or higher 4 4 TRIP CIRCUIT The main contacts will sa...

Page 8: ...igure 8 After plotting the steady state stability limit and the machine capability curves on the R X diagram plot the relay circle between the stability limit and the capability curve Note in figure 8...

Page 9: ...value S auto transformer primary tap value M auto transformer secondary tap value M is a per unit value determined by taking the sum of the values between the L and R leads The sign is positive when L...

Page 10: ...R lead in 0 03 tap and L lead in the upper 06 tap Since MC has plus sign lead L must be over R Then ohms or 98 of the desired value 5 3 UNDERVOLTAGE UNIT The undervoltage unit is usually set to a val...

Page 11: ...are applica tions where an external timer would be desirable 1 Cross compound units with undervoltage unit setting of 58 volts should use an exter nal timer to assure tripping before thermal damage ca...

Page 12: ...Since the link and connector screws carry operating current be sure that the screws are turned to bind snugly Compensator TC requires an additional setting for including or excluding the origin of R...

Page 13: ...er 06 03 0 0 Lower 06 0 03 0 0 03 0 Lower 06 0 0 03 Upper 06 Lower 06 Upper 06 Upper 06 Table 1 RECOMMENDED SETTINGS FOR KLF RELAY ZONE 1 ALONE ZONE 2 ALONE BOTH ZONE 1 ZONE 2 IMPEDANCE SETTING See Fi...

Page 14: ...I L 41 748 1F 14 NEG DC Figure 10 Generalized External Schematic Figure 11 Zone 1 Impedance Characteristic 3491A03 3491A03...

Page 15: ...I L 41 748 1F 15 Figure 12 Zone 2 Impedance Characteristic Figure 13 KLF 1 Frequency Response for Impedance Unit 3491A03 3491A09...

Page 16: ...se shifter for 90 current lag ging the voltage 3 With the terminal voltage at 50 volts increase current until contacts just close This current should be within 3 of 2 11 amp 2 20 2 05 amp 4 Adjust pha...

Page 17: ...ted to the 0 insert R lead should be connected to the upper 06 insert 03 06 06 15 between L R For the most accurate calibration preheat relay for at least an hour by energizing termi nals 4 5 6 7 with...

Page 18: ...p of 22 2 With relay deenergized adjust the restraint spring so that contact arm just floats 3 Maximum Torque Angle Check With 50 volts and 5 amperes applied vary the phase shifter to obtain the two a...

Page 19: ...d not be greater than the particular ICS tap settings being used The indicator target should drop freely G Telephone Relay Energize the telephone relay circuit terminals 10 and 3 with rated dc voltage...

Page 20: ...ompany Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 I L 41 748 1F Figure 14 Outline and Drilling Plan for the Type KLF 1 Relay in the FT 41 Case 57D7904 Den...