background image

I.L. 41-748.1F

11

dropout voltage of the undervoltage unit
should be set for 58 V

L-N

.

3. For all applications where the alarm function

is not to be used, the undervoltage unit con-
tact should be short circuited by means of a
jumper wire.

4. For industrial applications, with two or more

generators on the same bus, the undervolt-
age unit contact should be short circuited
and the alarm circuit not used.

5. For synchronous condenser and large motor

applications, the undervoltage unit contact
should, in general, be short circuited and the
alarm circuit not used. In general cases the
machine may be treated as in 2, above.

6. for gas turbine unites, with high generator

impedance, the undervoltage unit may not
operate. For these applications the under-
voltage contacts should be short circuited.

In cases where each generator is equipped with its
own transformer (unit connected) the standard fac-
tory setting of 53 VL-N (corresponding to 92.5 VL-L)
is usually satisfactory for the undervoltage unit. It
should operate at a level commensurate with the
minimum safe voltage for system stability.

NOTE: An electrical check of this particular set-

ting is outlined in this instruction leaflet,
under the heading “Acceptance Check”.

6. TIME DELAY CONSIDERATIONS

It may be conservatively stated that the rotor struc-
ture and stator heating, as a result of a shorted field
can be tolerated for 10 seconds on a conduc-
tor-cooled machine and 25 seconds for a conven-
tional machine. This time may be as low as 5
seconds for an open field (as opposed to a field
closed through a field discharged resistor on an
exciter armature) and as high as one minute where
the concern is protection of an adjacent tandem com-
pound unit against partial loss-of-excitation in the
faulted machine.

In view of the above considerations, it is often desir-
able to use an external timer in conjunction with the
KLF-1 Relay. The following examples are applica-
tions where an external timer would be desirable:

1.

Cross-compound units, with undervoltage

unit setting of 58 volts, should use an exter-
nal timer to assure tripping before thermal
damage can result. The timer is energized at
the alarm output and should be set for 10
seconds for a cross-compound conductor
cooled machine. For a conventionally cooled
cross-compound machine, the external timer
should be set for 25 seconds. As an alterna-
tive to this, the KLF-1 with shorted underolt-
age contacts may be applied and the alarm
feature not used. With this arrangement, trip-
ping takes place after the 250 ms time delay
provided by the X unit in the KLF-1 relay.

2. Machines connected to a common high volt-

age bus may be protected against partial
loss of voltage due to loss-of-excitation in an
adjacent machine by using a one-minute
timer driven by the alarm output of the
loss-of-field relay.

3.

In some critical applications 2-zone loss-of-field

protection may be desirable. In this case, the
zone-1 KLF-1 impedance circle should be
small and fully offset in the negative reactance
region. The long-reach should be set equal to
synchronous reactance, Xd. The short-reach
should be set equal to one-half transient reac-
tance, Xd1/2. The trip circuit should trip
directly, with no time delay. The alarm circuit
should operate a timer which may be set from
1/4 - 1.0 seconds, depending on use prefer-
ence. If the condition persists, this timer per-
mits tripping.

The second-zone KLF-1 may be set with a
larger impedance characteristic and will detect
partial loss-of-field conditions. A typical setting
would be to just allow the machine to operate
at maximum hydrogen pressure and .95 per
unit voltage. If a low voltage condition occurs, it
is recommended that tripping be accomplished
through a timer set for 3/4 second. Added to
the X unit dropout time of 1/4 second, this
gives an overall time of 1.0 second. If the volt-
age is maintained, then the alarm circuit
should start a “last ditch” timer. This timer may
be set anywhere from 10 seconds to one
minute, depending on machine type and use
preference.

Summary of Contents for KLF-1

Page 1: ...due to inadvert ent loss of potential such as due to a blown potential fuse On circuits with 3 phase 3 wire connected volt age transformers the type KLF relay is used 2 CONSTRUCTION The relay consists...

Page 2: ...I L 41 748 1F 2 Figure 1 Type KFL 1 Relay...

Page 3: ...e the magnetic core from the frame The electromagnet has two sets of two series con nected coils mounted diametrically opposite one another to excite each set of poles Locating pins on the electromagn...

Page 4: ...is attached to the moving contact arm by a spiral spring The spring adjuster is also held in place by a spring type clamp When contacts close the electrical connection is made through the stationary...

Page 5: ...ses the moving con tacts bridge two stationary contacts completing the trip circuit Also during this operation two fingers on the armature deflect a spring located on the front of the switch which all...

Page 6: ...ly by ZC Figure 6 assumes that ZC is positive circle includes origin If the current coil link is reversed the compensation becomes ZC In figure 6 b this change would result in VPOL being reduced rathe...

Page 7: ...the range of 60 to 100 percent of normal system voltage The actual range of adjustment is 40 to 70 VL N The dropout ratio of the unit is 98 percent or higher 4 4 TRIP CIRCUIT The main contacts will sa...

Page 8: ...igure 8 After plotting the steady state stability limit and the machine capability curves on the R X diagram plot the relay circle between the stability limit and the capability curve Note in figure 8...

Page 9: ...value S auto transformer primary tap value M auto transformer secondary tap value M is a per unit value determined by taking the sum of the values between the L and R leads The sign is positive when L...

Page 10: ...R lead in 0 03 tap and L lead in the upper 06 tap Since MC has plus sign lead L must be over R Then ohms or 98 of the desired value 5 3 UNDERVOLTAGE UNIT The undervoltage unit is usually set to a val...

Page 11: ...are applica tions where an external timer would be desirable 1 Cross compound units with undervoltage unit setting of 58 volts should use an exter nal timer to assure tripping before thermal damage ca...

Page 12: ...Since the link and connector screws carry operating current be sure that the screws are turned to bind snugly Compensator TC requires an additional setting for including or excluding the origin of R...

Page 13: ...er 06 03 0 0 Lower 06 0 03 0 0 03 0 Lower 06 0 0 03 Upper 06 Lower 06 Upper 06 Upper 06 Table 1 RECOMMENDED SETTINGS FOR KLF RELAY ZONE 1 ALONE ZONE 2 ALONE BOTH ZONE 1 ZONE 2 IMPEDANCE SETTING See Fi...

Page 14: ...I L 41 748 1F 14 NEG DC Figure 10 Generalized External Schematic Figure 11 Zone 1 Impedance Characteristic 3491A03 3491A03...

Page 15: ...I L 41 748 1F 15 Figure 12 Zone 2 Impedance Characteristic Figure 13 KLF 1 Frequency Response for Impedance Unit 3491A03 3491A09...

Page 16: ...se shifter for 90 current lag ging the voltage 3 With the terminal voltage at 50 volts increase current until contacts just close This current should be within 3 of 2 11 amp 2 20 2 05 amp 4 Adjust pha...

Page 17: ...ted to the 0 insert R lead should be connected to the upper 06 insert 03 06 06 15 between L R For the most accurate calibration preheat relay for at least an hour by energizing termi nals 4 5 6 7 with...

Page 18: ...p of 22 2 With relay deenergized adjust the restraint spring so that contact arm just floats 3 Maximum Torque Angle Check With 50 volts and 5 amperes applied vary the phase shifter to obtain the two a...

Page 19: ...d not be greater than the particular ICS tap settings being used The indicator target should drop freely G Telephone Relay Energize the telephone relay circuit terminals 10 and 3 with rated dc voltage...

Page 20: ...ompany Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 I L 41 748 1F Figure 14 Outline and Drilling Plan for the Type KLF 1 Relay in the FT 41 Case 57D7904 Den...

Reviews: