background image

I.L. 41-748.1F

10

2. Select a value of M that will most nearly

make it equal to:

.

If the sign is negative, then the M taps are connected
with the R lead above the L lead to raise the setting.

5.2.

SAMPLE CALCULATIONS

Assume that a KLF relay is to be applied to the fol-
lowing machine:

3-phase, 60 cycles, 3600 rpm, 18 kv, rated at 0.9 pf,
183,500 KVA at 45# H

2

.

R

C

 = 1400/1

R

V

 = 150/1

If the recommended setting from figure 8 is used:

The relay circle needed for a particular set of
machine capability curves may be obtained by trial
and error using a compass. The offset and radius of
the relay circle in figure 8 were drawn by this method.

Z

A

 per unit = 1.68

Z

C

 per unit = 2R -Z

A

 = 2 x 0.94 -1.68 = 0.20

(1)

= 16.45 ohms

(2)

= 27.6 ohms

(3)

= 3.29 ohms

To set Z

A

 = 27.6 ohms

Step 1:

The lowest tap S

A

 for 18.6 S

A

 greater than

Z

A

 = 27.6 is 2. Set S

A

 in tap 2.

Step 2:

T

A

 nearest to

 = 13.8 is T

A

 = 15.8.

Set TA in 15.8 tap.

Step 3:

 

=

1.145 -1 = + .145

Set M = + .15. Place R lead in O, L lead in upper .06.
The relay setting is now:

Actual

This is 99% of the desired setting.

To set Z

C

 = 3.29 ohms:

Step 1:

The lowest tap S

C

 for 6S

C

 greater than

3.29 is S

C

 = 1

Set S

C

 = 1

Step 2:

T

C

 nearest to

Set T

C

 in 3.64 tap.

Step 3:

= 1.107 -1 = +.107

Hence, the nearest M

C

 value is +.12. Now set R lead

in 0.03 tap and L lead in the upper .06 tap.

(Since M

C

 has plus sign, lead L must be over R).

Then,

 ohms, or

98% of the desired value.

5.3.

UNDERVOLTAGE UNIT

The undervoltage unit is usually set to a value corre-
sponding to the minimum safe system voltage for
stability. The voltage depends on many factors, but is
usually between 70 and 80 percent of normal system
voltage. The undervoltage unit is set at the factory for
77 percent of normal system voltage, or 53 volts
line-neutral. In applications where multiple units are
connected to the same bus, loss-of-field of one unit
may not depress the bus voltage of the point where
the undervoltage unit will operate if it has the stan-
dard setting. The following recommendations should
be considered:

1.

For cross-compound turbine generator appli-

cations, the dropout (contact closure of
“back” contact of voltage unit, i.e., the con-
tact which is in the trip circuit and is shown
closed on schematic) voltage of the under-
voltage unit should be set for 58 V

L-N

 (equiv-

alent to 100 V

L-L

).

2. For water wheel generator applications, with

multiple machines tied to a common bus, the

M

TS

Z

------

1

=

Z

base

1000

kv

( )

2

R

C

kva

(

)

R

V

-----------------------------------

1000

18

( )

×

2

1400

×

183 500

150

×

,

------------------------------------------------------

=

=

Z

A

Z

A

per unit

(

)

Z

base

(

)

1.68

(

)

16.45

(

)

=

=

Z

C

Z

C

per

unit

(

)

Z

base

(

)

0.20

(

)

16.45

(

)

=

=

27.6

2

-----------

M

A

T

A

S

A

Z

--------------

1

=

15.8

2

×

27.6

---------------------

1

Z

A

T

A

S

A

1

M

±

--------------

15.8

2

×

1

0.15

+

---------------------

31.6
1.15

-----------

27.5

=

=

=

=

3.29

1

-----------

3.29 is 3.64

=

M

C

T

C

S

C

Z

C

---------------

1

3.64

1

×

3.29

---------------------

1

=

=

Z

C

T

C

S

C

1

M

C

+

(

)

-----------------------

3.64

1

×

1

.12

˙

+

---------------------

3.25

=

=

=

Summary of Contents for KLF-1

Page 1: ...due to inadvert ent loss of potential such as due to a blown potential fuse On circuits with 3 phase 3 wire connected volt age transformers the type KLF relay is used 2 CONSTRUCTION The relay consists...

Page 2: ...I L 41 748 1F 2 Figure 1 Type KFL 1 Relay...

Page 3: ...e the magnetic core from the frame The electromagnet has two sets of two series con nected coils mounted diametrically opposite one another to excite each set of poles Locating pins on the electromagn...

Page 4: ...is attached to the moving contact arm by a spiral spring The spring adjuster is also held in place by a spring type clamp When contacts close the electrical connection is made through the stationary...

Page 5: ...ses the moving con tacts bridge two stationary contacts completing the trip circuit Also during this operation two fingers on the armature deflect a spring located on the front of the switch which all...

Page 6: ...ly by ZC Figure 6 assumes that ZC is positive circle includes origin If the current coil link is reversed the compensation becomes ZC In figure 6 b this change would result in VPOL being reduced rathe...

Page 7: ...the range of 60 to 100 percent of normal system voltage The actual range of adjustment is 40 to 70 VL N The dropout ratio of the unit is 98 percent or higher 4 4 TRIP CIRCUIT The main contacts will sa...

Page 8: ...igure 8 After plotting the steady state stability limit and the machine capability curves on the R X diagram plot the relay circle between the stability limit and the capability curve Note in figure 8...

Page 9: ...value S auto transformer primary tap value M auto transformer secondary tap value M is a per unit value determined by taking the sum of the values between the L and R leads The sign is positive when L...

Page 10: ...R lead in 0 03 tap and L lead in the upper 06 tap Since MC has plus sign lead L must be over R Then ohms or 98 of the desired value 5 3 UNDERVOLTAGE UNIT The undervoltage unit is usually set to a val...

Page 11: ...are applica tions where an external timer would be desirable 1 Cross compound units with undervoltage unit setting of 58 volts should use an exter nal timer to assure tripping before thermal damage ca...

Page 12: ...Since the link and connector screws carry operating current be sure that the screws are turned to bind snugly Compensator TC requires an additional setting for including or excluding the origin of R...

Page 13: ...er 06 03 0 0 Lower 06 0 03 0 0 03 0 Lower 06 0 0 03 Upper 06 Lower 06 Upper 06 Upper 06 Table 1 RECOMMENDED SETTINGS FOR KLF RELAY ZONE 1 ALONE ZONE 2 ALONE BOTH ZONE 1 ZONE 2 IMPEDANCE SETTING See Fi...

Page 14: ...I L 41 748 1F 14 NEG DC Figure 10 Generalized External Schematic Figure 11 Zone 1 Impedance Characteristic 3491A03 3491A03...

Page 15: ...I L 41 748 1F 15 Figure 12 Zone 2 Impedance Characteristic Figure 13 KLF 1 Frequency Response for Impedance Unit 3491A03 3491A09...

Page 16: ...se shifter for 90 current lag ging the voltage 3 With the terminal voltage at 50 volts increase current until contacts just close This current should be within 3 of 2 11 amp 2 20 2 05 amp 4 Adjust pha...

Page 17: ...ted to the 0 insert R lead should be connected to the upper 06 insert 03 06 06 15 between L R For the most accurate calibration preheat relay for at least an hour by energizing termi nals 4 5 6 7 with...

Page 18: ...p of 22 2 With relay deenergized adjust the restraint spring so that contact arm just floats 3 Maximum Torque Angle Check With 50 volts and 5 amperes applied vary the phase shifter to obtain the two a...

Page 19: ...d not be greater than the particular ICS tap settings being used The indicator target should drop freely G Telephone Relay Energize the telephone relay circuit terminals 10 and 3 with rated dc voltage...

Page 20: ...ompany Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 I L 41 748 1F Figure 14 Outline and Drilling Plan for the Type KLF 1 Relay in the FT 41 Case 57D7904 Den...

Reviews: