background image

I.L. 41-748.1F

12

7. SETTING THE RELAY

The type KLF-1 relay requires a setting for each of
the two compensators T

A

 and T

C

, for each of the two

auto-transformers primaries S

A

 and S

C

, and for the

undervoltage unit.

7.1.

GENERAL SETTING RECOMMENDATIONS

The KLF relay may be applied as a single-zone
device, or two relays may be used to provide
two-zone protection. The single-zone setting may be
fully offset (Zone-1) or may include the origin
(Zone-2). The two-zone application would require a
Zone-1 KLF and a Zone-2 KLF, approximately equiv-
alent to two-zone step-distance line protection. A
generalized external schematic, which is applicable
to either Zone-1 or Zone-2 relays is shown in figure
9. The recommended settings and relative advan-
tages of these various configurations are summa-
rized in Table 1.

The single-zone and two-zone setting recommenda-
tions are modified when two or more machines are
bussed at the machine terminals.The voltage and
time delay considerations are treated in detail in
other sections of this leaflet. The recommended set-
tings are outlined in Table 2.

7.2.

COMPENSATOR (T

A

 AND T

C

)

Each set of compensator taps terminates in inserts
which are grouped on a socket and form approxi-
mately three-quarters of a circle around a center
insert which is the common connection for all taps.
Electrical connections between common insert and
tap inserts are made with a link that is held in place
with two connector screws, one in the common and
one in the tap.

A compensator tap setting is made by loosening the
connector screw in the center. Remove the connec-
tor screw in the tap end of the link, swing the link
around until it is in position over the insert for the
desired tap setting, replace the connector screw to
bind the link to this insert, and retighten the connec-
tor screw in the center. Since the link and connector
screws carry operating current, be sure that the
screws are turned to bind snugly.

Compensator T

C

 requires an additional setting for

including or excluding the origin of R-X diagram from
the distance unit characteristic. If the desired charac-
teristic is similar to that shown on figure 5(b), the

links should be set vertically in the +T

C

 arrow direc-

tion. If a characteristic similar to that shown in figure
5(c) is desired, set links horizontally in the -T

C

 arrow

direction.

7.3.

AUTO-TRANSFORMER PRIMARY
(S

A

 AND S

C

)

Primary tap connections are made through a single
lead for each transformer. The lead comes out of the
tap plate through a small hole located just below the
taps and is held in place on t he proper tap by a con-
nector screw.

An S setting is made by removing the connector
screw, placing the connector in position over the
insert of the desired setting, replacing and tightening
the connector screw. The connector should never
make electrical contact with more than one tap at a
time.

7.4.

AUTO-TRANSFORMER SECONDARY
(M

A

 AND S

C

)

Secondary tap connections are made through two
leads identified as L and R for each transformer.
These leads come out of the tap plate each through
a small hole, one on each side of the vertical row of
M tap inserts. The lead connectors are held in place
on the proper tap by connector screws.

Values for which an M setting can be made are from
-.15 to +.15 in steps of .03. The value of a setting is
the sum of the numbers that are crossed when going
from the R lead position to the L lead position. The
sign of the M value is determined by which lead is in
the higher position on the tap plate. The sign is posi-
tive (+) if the L lead is higher and negative (-) if the R
lead is higher.

An M setting may be made in the following manner:
Remove the connector screws so that the L and R
leads are free. Determine from the following table the
desired M value and tap positions. Neither lead con-
nector should make electrical contact with more than
one tap at a time.

Summary of Contents for KLF-1

Page 1: ...due to inadvert ent loss of potential such as due to a blown potential fuse On circuits with 3 phase 3 wire connected volt age transformers the type KLF relay is used 2 CONSTRUCTION The relay consists...

Page 2: ...I L 41 748 1F 2 Figure 1 Type KFL 1 Relay...

Page 3: ...e the magnetic core from the frame The electromagnet has two sets of two series con nected coils mounted diametrically opposite one another to excite each set of poles Locating pins on the electromagn...

Page 4: ...is attached to the moving contact arm by a spiral spring The spring adjuster is also held in place by a spring type clamp When contacts close the electrical connection is made through the stationary...

Page 5: ...ses the moving con tacts bridge two stationary contacts completing the trip circuit Also during this operation two fingers on the armature deflect a spring located on the front of the switch which all...

Page 6: ...ly by ZC Figure 6 assumes that ZC is positive circle includes origin If the current coil link is reversed the compensation becomes ZC In figure 6 b this change would result in VPOL being reduced rathe...

Page 7: ...the range of 60 to 100 percent of normal system voltage The actual range of adjustment is 40 to 70 VL N The dropout ratio of the unit is 98 percent or higher 4 4 TRIP CIRCUIT The main contacts will sa...

Page 8: ...igure 8 After plotting the steady state stability limit and the machine capability curves on the R X diagram plot the relay circle between the stability limit and the capability curve Note in figure 8...

Page 9: ...value S auto transformer primary tap value M auto transformer secondary tap value M is a per unit value determined by taking the sum of the values between the L and R leads The sign is positive when L...

Page 10: ...R lead in 0 03 tap and L lead in the upper 06 tap Since MC has plus sign lead L must be over R Then ohms or 98 of the desired value 5 3 UNDERVOLTAGE UNIT The undervoltage unit is usually set to a val...

Page 11: ...are applica tions where an external timer would be desirable 1 Cross compound units with undervoltage unit setting of 58 volts should use an exter nal timer to assure tripping before thermal damage ca...

Page 12: ...Since the link and connector screws carry operating current be sure that the screws are turned to bind snugly Compensator TC requires an additional setting for including or excluding the origin of R...

Page 13: ...er 06 03 0 0 Lower 06 0 03 0 0 03 0 Lower 06 0 0 03 Upper 06 Lower 06 Upper 06 Upper 06 Table 1 RECOMMENDED SETTINGS FOR KLF RELAY ZONE 1 ALONE ZONE 2 ALONE BOTH ZONE 1 ZONE 2 IMPEDANCE SETTING See Fi...

Page 14: ...I L 41 748 1F 14 NEG DC Figure 10 Generalized External Schematic Figure 11 Zone 1 Impedance Characteristic 3491A03 3491A03...

Page 15: ...I L 41 748 1F 15 Figure 12 Zone 2 Impedance Characteristic Figure 13 KLF 1 Frequency Response for Impedance Unit 3491A03 3491A09...

Page 16: ...se shifter for 90 current lag ging the voltage 3 With the terminal voltage at 50 volts increase current until contacts just close This current should be within 3 of 2 11 amp 2 20 2 05 amp 4 Adjust pha...

Page 17: ...ted to the 0 insert R lead should be connected to the upper 06 insert 03 06 06 15 between L R For the most accurate calibration preheat relay for at least an hour by energizing termi nals 4 5 6 7 with...

Page 18: ...p of 22 2 With relay deenergized adjust the restraint spring so that contact arm just floats 3 Maximum Torque Angle Check With 50 volts and 5 amperes applied vary the phase shifter to obtain the two a...

Page 19: ...d not be greater than the particular ICS tap settings being used The indicator target should drop freely G Telephone Relay Energize the telephone relay circuit terminals 10 and 3 with rated dc voltage...

Page 20: ...ompany Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 I L 41 748 1F Figure 14 Outline and Drilling Plan for the Type KLF 1 Relay in the FT 41 Case 57D7904 Den...

Reviews: