Information: Alarm Connections
Connector
J1
-
Controller Variants
Pin
0I5R_D (5 Relays),
3C3R 3 Inputs, 3 Relays,
9C0R_USB 9 Inputs, no Relays
1
Output: R3 = Rtn
Input: PBT/TR
Input: Door Open
2
Output: R2 = Rtn
Input: Hi Ext. Temp.
Input: Surge Protect Fail
3
Output: R1 = Rtn
2
Output: R1 = Rtn
Input: Door 2 Open
4
Output: PMN Rtn
Output: PMN Rtn
Input: Ext DC Fail Major
5
Output: PMJ Rtn
Output: PMJ Rtn
Input: Ext DC Fail Minor
6
Output: R3 = ACF
Input: RTNS
Input: Returns
7
Output: R2 = RFA
Input: Cust. Alrm 1
Input: Retrieve Generator
8
Output: R1 = BD
Output: R1 = BD
Input: Battery Fail
9
Output: PMN
Output: PMN
Input: Air Conditioner Fail
10
Output: PMJ
Output: PMJ
Input: External Fan Fail
Connector
J2
Pin
All Controllers
1
Input: SPD Fail
2
—
3
Input: AUX MAJ
4
Input: Air Cond. Fail
5
Input: Door Open
6
-
48V
7
-
48V
8
-
48V
9
Output: R4 = FAJ
1
10
Output: R4 = Rtn
1,2
Alarm connections are on the rear of the shelf
-
J1 is Alarm Outputs and J2 is Alarm Inputs. Change alarm
descriptions via LAN port (Web pages) or Craft port (EasyView2) when required.
Table 4: J1 Alarm Connections
Table 5: J2 Alarm Connections
Information: Fault Detection
Circuit ON: Output is powered unless over loaded (power exceeds 100VA). Overloads are retested every 4 sec.
Circuit OFF: Output is unpowered.
Circuit Load Detection:
Circuits are scanned for loads upon module power up and upon manual scan.
Circuits with loads are turned ON, circuits without loads are turned OFF.
Circuit ON/OFF status is only set by scans and Manual Circuit ON/OFF actions. The last action determines the ON/
OFF state of each circuit. The only automatic change in circuit ON/OFF status occurs upon module power up.
Information –
Rectifier Basic Information
Rectifier
Single phase, hot
-
pluggable, fan
-
cooled
Input
Recommended
AC Breaker
Output
Vac
A
A
Float
Vdc
W
A
CC109165610
EP1600
-
UTEZ: 1600W
100
-
120
15
20
48
-
58
1200
24
200
-
240
7.5
10
48
-
58
1600
32
Table 6: Rectifier and Plant Data
Note: Output Current at 54.5V. Outputs are power limited, not current limited.
1
Only with 6 relay controllers (...6R
…).
2
Returns for R1 and R4 are bridged. Other returns are isolated.
QUICK START GUIDE