Information: Circuit ON/OFF and Load Detection
Circuit ON: Output is powered unless over loaded (power exceeds 100VA). Overloads are retested every 4 sec.
Circuit OFF: Output is unpowered.
Circuit Load Detection:
Circuits are scanned for loads upon module power up and upon manual scan.
Circuits with loads are turned ON, circuits without loads are turned OFF.
Circuit ON/OFF status is only set by scans and Manual Circuit ON/OFF actions. The last action determines the ON/
OFF state of each circuit.
The only automatic change in circuit ON/OFF status occurs upon module power up.
Information: Manual Module Operations
Manually Scan Circuit Loads: Press and release the Button
-
no interruption of power to ON circuits.
Manual Circuit ON/OFF:
1.
Press and hold the Button to enter the manual mode hold until the OK LED turns OFF and back ON
(2 seconds)
1.
Tap the Button repeatedly until the desired Circuit LED blinks.
Circuit ON
-
LED ON with brief blink OFF
Circuit OFF
-
LED OFF with brief blink ON
3.
Press and hold the Button to toggle the circuit ON/OFF hold until the OK LED turns OFF and back ON
(2 seconds)
3.
Repeat from step 2 to operate another circuit.
4.
Automatic operation is restored after a few seconds of Button inactivity.
The OK LED is turned OFF when the button is pressed. It returns to ON when the button is released or after
the
button is held for 2 seconds.
Circuit LED
Converter Button
Figure 18: Module LEDs & Button