![ABB J2007003L301A Quick Start Manual Download Page 14](http://html.mh-extra.com/html/abb/j2007003l301a/j2007003l301a_quick-start-manual_2837989014.webp)
Page 14
© 2021 ABB. All rights reserved.
Version 1.0
Step 9
-
Install 1
-
Wire Battery Temp and Voltage Monitor per Galaxy Pulsar Edge
Controller Quick Start Guide
-
Optional
Connect 1
-
Wire Battery Temp and Voltage Monitor to upper DATA connector (J3) of SPS PE shelf.
Step 10
-
Install Rectifiers
•
Firmly push the rectifier module EP1600
-
UTEZ RECTIFIER
into the rectifier slot.
•
Tighten the thumb screw until the rectifier is seated.
NOTE: When installing a rectifier in a powered system the RUN
LED on the rectifier will blink until communication with the con-
troller is established.
Step 12
-
Install Converter Modules
•
Verify Module Type
-
PE 8CKT LMT MODULE (150027362 ). There are two converter modules to be fixed in the
converter shelves provided.
•
Open the latch of the converter module.
•
Insert module into the respective slot of the Shelf.
•
Close the latch of the converter module.
Step 11
-
Verify Shelf ID Setting
•
Set Shelf ID to 00 to operate without a system controller.
•
Set Shelf ID to 01 through 98 are read by a controller if
present.
•
Set Shelf ID to 99 to perform Lamp Test.
Step 13 –
Initial Start Up
•
Verify that all AC, DC and Alarm connections are complete and secure.
•
Turn on the AC input breakers.
•
If there are no alarms, make required adjustments to the default settings on the controller for this installation.
Figure 13: Rectifier Installation
Figure 14: Shelf ID setting
Figure 15: Converter Module Installation
QUICK START GUIDE