KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
31
12.3.1 Common parameter – Activate device locking/unlocking by group object
Options
Inactive
1 for locking – 0 for unlocking
0 for locking – 1 for unlocking
This parameter is used to specify whether lock and unlock of the complete device can be
activated from the KNX bus line. It defines the action of the 1 bit communication object.
Note: This parameter is only visible if “Locking function selection – Device locking”
is activated.
12.3.2 Object no
Object name
Data type
Flags
DL: Device locking GO
1 bit DPT 1.001
C, W, U
12.4
Application “Energy saving/Primary function”
The control element has the features of energy saving and trigger of the primary function.
After non-actuation of the control element, the brightness of the LCD display screen will
switchover to minimum/off brightness. Primary function – send telegram when any of the
button is trigger when control element enter energy saving function.
12.4.1 Common parameter – Button first press function when control element is in energy
saving mode
Options
Awake
Awake and send command
This parameter is used to specify to define what is the first action when the rocker is press
when the control element is in energy saving state.
Awake – control element LCD will light up only and wait for next press on the rocker to
send command.
Awake and send command - control element LCD will light up and send the command
that is configure on the rocker that is press.
12.4.2 Common parameter – Delay time for switchover, active to energy saving (sec)
Options
Input from 1 sec to 255 sec
This parameter is used to specify the duration for control element to switchover to energy
saving mode after non-actuation of the control element.
12.4.3 Common parameter – Energy saving/Primary functions activate/deactivate by
group object
Options
Inactive
1 = activate / 0 = deactivate