HVC 450 kW E-Bus Charger Installation Guide
Revision: 1.2
COMPANY CONFIDENTIAL
Date released: 16-08-2018
Page
75
of
128
Interlock cable connection in slave 1
HVC 150S
:
A
Terminal block
B
Interlock cable from/to slave 2 HVC 150S
C
Interlock cable from/to master HVC 150
1. Move the cables towards the terminal block (A).
2. Strip 0.43 Inch of the insulation from the ends of the wires.
3. Crimp a ferrule onto the end of the wire.
4. Loosen the connector screws.
5. Insert the wires into the connectors, see table below:
Functional description
Connector
Wire number
Interlock In (master HVC 150)
X286-4
2
Interlock Out (master HVC 150)
X286-6
1
Interlock GND (master HVC 150)
X286-9
Shield
Interlock In (slave 2 HVC 150S)
X286-7
1
Interlock Out (slave 2 HVC 150S)
X286-8
2
Interlock GND (slave 2 HVC 150S)
X286-5
Shield
See also Appendix H
Signal connection diagram
.
6. Tighten the connector screws.