FSM4000
ELECTROMAGNETIC FLOWMETER | OI/FSM4000-EN REV. E
43
Bus address
The bus address is automatically assigned or can be set in the
system manually.
Addresses are detected using a unique combination of
manufacturer ID, device ID, and device serial number.
System integration
The following are required:
• DD (Device Description) file, which includes the device
description.
• CFF (Common File Format) file is required for engineering
the segment. Engineering can be performed online or
offline.
For additional information, see the separate interface
description.
The files required for operation can be downloaded from
Connection examples for peripherals
(incl. HART)
Current output
I
internal
E
external
Figure 41: Current output active with / without HART protocol (4 ... 20 mA)
Current output active with / without HART protocol (4 ... 20 mA)
Terminals
31, 32
Current output
can be selected via software
Function
Active
0/4 ... 20 mA (0 Ω ≤ RB ≤ 560 Ω)
0/2 ... 10 mA (0 Ω ≤ RB ≤ 1120 Ω)
(for HART only 4 ... 20 mA)
Switch output
I
internal
E
external
Figure 42: Switch output for system monitoring, Max. / Min. alarm for empty meter tube
or forward / reverse signal
Switch output for system monitoring
Terminals
41, 42
Current output
can be selected via software
Function
Passive
• ‘closed’:
0 V ≤ UCEL ≤ 2 V, 2 mA ≤ ICEL ≤ 220 mA
• ‘open’:
16 V ≤ UCEH ≤ 30 V, 0 mA ≤ ICEH ≤ 2
mA
Note
Horn and alarm light are shown only as examples. Other suitable
devices such as bells, sirens, buzzers, etc., can also be used.