92
FSM4000
ELECTROMAGNETIC FLOWMETER | OI/FSM4000-EN REV. E
… 8 Operation
… Parameter descriptions
Submenu / parameter
Value range
Remark
Submenu
Preselect the diagnostic measurement values that you want
to display and manage in the Fingerprint data.
Fingerprint
Submenu
Assign the rate for Fprt1. The display line for the process
indicator is assigned in the submenu.
Fprt1
Diagnostic
Value
AC Volt. coil;
AC Current coil;
ohm. res. coil;
Temp. coil;
ins. res. coil;
Volt. E1; Volt. E2;
Electr. balan.;
Magn. linear;
SNR noise ratio;
Max. DAC value;
Oprtg. hrs trn;
Oprtg. hrs sens
Select the value:
AC Volt. Coil:
Coil voltage AC
AC Current Coil:
Coil current AC
ohm. res. Coil:
Ohmic resistance of coil
Temp. coil:
Coil temperature
ins. res. Coil:
Insulation resistance of coil
Volt. E1:
AC voltage at electrode 1
Volt. E2:
AC voltage at electrode 2
Electr. balan.:
Electrode balance
Magn Linear:
Magnetic linearity
SNR Noise ratio:
Signal-to-noise ratio
Max DAC value:
Maximum DAC value
Oprtg. hrs trn::
Operating hours for transmitter
Oprtg. hrs sens::
Operating hours for sensor
These values are updated only if the status was set to
Warning or Error in the ‘Alarm Settings’ submenu.
AC Volt. coil
Data set
Current; Prod1;
Prod2; Startup;
Factory;
Hist1; Hist2; Hist3;
Hist4; Hist5; Hist6;
Hist7; Hist8; Hist9
Current: Data set for current measured value
Prod1:
Product1 fingerprint
Prod2:
Product2 fingerprint
Start-up: Commissioning fingerprint
Default: Default fingerprint
Hist1-9: Data set 1 ... 9 for the preceding
measured values
Current
Submenu
As for Fprt1
Assign the rate for Fprt1. The display line for the process
indicator is assigned in the submenu.
Fprt4