![ABB Focus II FII-4-14 Series Original Instructions Manual Download Page 35](http://html.mh-extra.com/html/abb/focus-ii-fii-4-14-series/focus-ii-fii-4-14-series_original-instructions-manual_4042035.webp)
35
www.abb.com/lowvoltage
2TLC172015M0201, rev. D
8 Pre-reset function
NB!
The Pre-reset function is an addition to the manual reset function. It can be used, where the operator
doing the reset is not able to see the entire hazardous zone.
The pre-reset pushbutton must be installed in the (hazardous) zone from where the operator is able to
check that nobody else is in the hazardous zone before the manual reset function is used. Failure to do so
may result in serious injury.
•
Pre-reset function sets the Focus II system to manual reset mode.
•
Blanking function can not be selected using pre-reset function.
•
Muting function can not be selected using pre-reset function.
•
The time limit between pre-reset and manual reset is 8 s.
Pre-reset setup and connection example
•
Enable pre-reset mode with the internal change-over switches (See 4.4).
•
Connect a pre-reset button
to MUTING A input (green) and +24 VDC to MUTING B input (yellow).
Pre-reset sequence
1.
Press pre-reset button. LED 5 flashes once per second.
2. <8 s to execute step 3 and 4.
3. Pass through the detection zone.
4. Press reset button.
5. OSSD to on.
1
2
3
4
5
Brown
+24VDC
Blue
0V
Brown
+24VDC
Blue
0V
1
2
3
4
5
6
7
8
White
Test / Reset
Green
Yellow
OSSD 1 (RL 500mA max.)
OSSD 2 (RL 500mA max.)
Grey
Pink
Red
Screen
Ground
Screen
Ground
1
White
Black
Grey
Pre-reset
3
T
ransmitter
Receiver
M12
Cable