6.2 Muting, Modes
The Focus II system offers a set of three muting modes:
•
T-muting activation (default) with time limit
•
L-muting activation with time limit
•
X-muting activation without time limit
NB!
Additional settings are possible for light grids (FII-4-K...), see 4.4.
1. T-, L-muting: Muting sensor A must be activated before muting sensor B. X-muting: Either A och B can be activated first.
2. Additional settings/timings available for Focus II light grids, see 4.4.
3. The maximum time that Focus II will allow muting A or muting B to drop without detecting a muting stop.
Features - Muting grid
Bypassing of light curtain or grid in one or two directions (L-form, T-form). Connected directly via a M12
cable to light curtain/grid.
Muting type
Sensor type (A,B)
Timings
A-B time
1
Max muting time
2
Allowed drop
2,3
T
NO, NO
0.03 s < t <120 s
<600 s
<0.2 s
L
NO, NO
0.03 s < t <120 s
<600 s
<0.2 s
X
NO, NC
2
0 s < t <4 s
2
Infinite
<0.2 s