Section-10
04-3006_S10_TDS_ABB_DPA_UPSCALE_RI_10-80kW_EN_150316.doc
Page 9/16 ABB
Modifications reserved
10.6 ENVIRONMENTAL CHARACTERISTICS
Module type
unit
UPScale M 10
UPScale M 20
Module rated power
kW
10
20
Operation temperature
°C
0 - 40
Ambient Temperature for Batteries (recommended)
°C
20 - 25
Storage Temperature
°C
-25 - +70
Battery Storage Time at Ambient Temperature
Max. 6 months
Max. altitude (above sea level) without de-rating
m/feet 1000 / 3300ft
De-rating factor for use at altitudes above 1000m
sea level according (IEC 62040-3)
m/feet
(meter / feet) above sea level
De-Rating Factor for Power
1500 / 4850
0.95
2000 / 6600
0.91
2500 / 8250
0.86
3000 / 9900
0.82
Relative Air-humidity
Max. 95% (non-condensing)
UPS Positioning
See chapter 10.11
Input and Output Power Cabling
From the bottom on the front
Efficiency AC-AC up to (at cosphi 1.0)
(tol/- 0.5% applies on all figures)
%
Load
:
100 %
75 %
50%
25%
M20&M10 : 95.5% 95.5%
95%
94.5%
Efficiency with Linear Load at cosphi =0.8 ind
Efficiency Non-linear Load (IEC/EN 6240-3)
Typically up to 1 % higher of above values
Typically up to 1 % lower of above values
Eco-Mode efficiency at 100% load
%
98 %
10.7 STANDARDS
Safety
EN 62040-1-1, EN 60950-1
Electromagnetic Compatibility
EN 61000-6-4 Prod.standard: EN 62040-2
EN 61000-6-2 Prod.standard: EN 62040-2
EN 61000-4-2, EN 61000-4-3 - EN 61000-4-4 - EN 61000-4-5 - EN 61000-4-6
EMC Classification,
Emission Class
C3
Immunity Class
C3
Performance
IEC/EN 62040-3
Product certification
CE
Degree of protection
IP 20
Summary of Contents for DPA Upscale M 10
Page 27: ......
Page 28: ......
Page 29: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 51: ......
Page 52: ......
Page 53: ......