ControlMaster CM10, CM30 and CM50
Universal process controllers,
1
/
8
,
1
/
4
and
1
/
2
DIN
7 Advanced Level
74
IM/CM/S–EN Rev. R
…Profile Parameters / …Common Settings / …Program Control
Recovery
Action
Selects the profile restart action when power is restored after a failure or the PV is restored
after a failure and the
Recovery Period
(
Time
– see below) has expired.
Continue
The program resumes from the point at which failure occurred and is placed in
Operator Hold
mode.
Repeat
The program resumes from the start of the current segment and is placed in
Operator Hold
mode.
Reset
The program resumes from the start of the current program and is placed in
Operator Hold
mode.
Advance
The program resumes at the point in the program that would have been reached if no power
failure had occurred in
Run
mode.
Note
. If a zero time period is selected the program will always recover with the chosen option.
Time
Set the recovery time period used to determine the recovery action.
The time is configurable in HH:MM:SS.