ControlMaster CM10, CM30 and CM50
Universal process controllers,
1
/
8
,
1
/
4
and
1
/
2
DIN
7 Advanced Level
IM/CM/S–EN Rev. R
57
…Control / …Loop 1 Output / …Failure Actions / …Power Recovery
Man – Default
Manual
control mode with output set to default value.
Auto Mode
Auto
control mode with integral term reset.
Auto – Last
Auto
control mode with integral term restored to its last value before the power failure.
PV Fail Action
Determines the controller output when the PV (process variable) input fails.
No Action
No action is taken if the PV input fails.
Man – Hold
O/P
Puts the controller into
Manual
control mode and holds the output at its value immediately prior to
the PV failure.
Man – Default
O/P
Puts the controller into
Manual
control mode and sets the output to the default output value.
Default Output
This parameter is used in conjunction with
Power Recovery
(see page 56) and
PV Fail Action
settings (see above). For split outputs this value refers to the
PID
algorithm (see page 30) before
the split range values are calculated.