ControlMaster CM10, CM30 and CM50
Universal process controllers,
1
/
8
,
1
/
4
and
1
/
2
DIN
7 Advanced Level
56
IM/CM/S–EN Rev. R
…Control
Loop 1 Output
Used to set the output limits, tracking rates, slew rates and output action on power failure or
process variable failure.
Limits
Note
. When used with split output the limits restrict the
PID
algorithm output (see page 30) before
the split output range values are calculated.
Limit Action
Selects when the output limits should be applied (
Off
,
Auto + Manual
,
Auto Only
).
Low/High Limit
Sets minimum / maximum controller output in %.
Failure Actions
Power Recovery
Used to select the default power failure mode required following a power interruption or failure.
Last Mode
The last
Power Recovery
mode selected.
Man – Last
Manual
control mode using the last output before power failure.
Man – 0 %
Manual
control mode with output set to 0 %.
Man – 100 %
Manual control mode with output set to 100 %.