ControlMaster CM10, CM30 and CM50
Universal process controllers,
1
/
8
,
1
/
4
and
1
/
2
DIN
7 Advanced Level
58
IM/CM/S–EN Rev. R
…Control / …Loop 1 Output
A/M Select Sources
The selection of A/M (
Auto / Manual
) control modes of operation can be controlled by digital
signals; either from internal digital signals (for example, alarm states) or from external signals via
digital inputs (or digital communications).
Auto Select
The source required to select
Auto
control mode. Selection
is made on the rising edge of the digital signal.
Manual 1 (2)
Select
The source required to select
Manual
control mode.
Selection is made on rising edge of the digital signal. The
output value is set according to
Manual 1 (2) Config O/P
(see
below).
Manual 1 (2)
Output
Determines the Manual output value to be set when the controller is put into
Manual
control mode
(see page 5) using
Manual 1 (2) Select
source.
Last Auto O/P
Holds the output at its value prior to switching to
Manual
control mode.
Man – 0%
Sets the output to 0 %.
Man – 100%
Sets the output to 100 %.
Config Value
Sets the output to the value set in
Manual 2 Config O/P
.
Auto
Control Mode
Manual