…Control / …Loop 1 Setpoints
RSP Fault Action
The action required when a fault occurs with the remote setpoint.
No Action
No fault action.
Local
Selects the local (internal) setpoint mode.
Local Default
Selects the local (internal) setpoint mode and sets its value to the default setpoint.
Default Setpoint
Sets the value required for the local (internal) setpoint under remote setpoint fault conditions.
Ramp Mode
See
Basic
Level, page 28.
Ramp Rate
See
Basic
Level, page 28.
Select Sources
Selection of local setpoints and changing the setpoint mode (between local [internal] and remote
[external]) can be controlled by digital signals; either from internal digital signals (for example, alarm
states) or from external signals via digital inputs (or digital communications) – see Appendix A.1,
page 116 for description of sources.
LSP 1/2 Toggle
The (level-triggered) source required to select either local
setpoint 1 (LSP1) or local setpoint 2 (LSP2). A low signal locks the
local setpoint as LSP1; a high signal locks it as LSP2.
LSP1
LSP1
LSP2