Description of application and parameters
Application "Function block x"
Product manual 2CKA001473B9679
│274
11.7.17.7
Send Eco object
Options:
Deactivated
Activated
■
Deactivated:
– No telegram is sent via object "Sx: Eco operating mode" at the press of the operating
mode switchover button.
■
Activated:
– A telegram is sent via object "Sx: Eco operating mode" at the press of the operating
mode switchover button.
– The telegram that is sent, always has the inverted value of the value sent last. This
means that "0" or "1" is sent (toggle mode) alternately via object "Sx: comfort operating
mode" at each press of the button.
The parameter is used to specify whether a telegram is sent on the bus via the 1-bit
communication object "Sx: Eco operating mode" when the operating mode switchover button is
pressed. This may be necessary for switching the linked room temperature controller (RTC) into
a defined operating mode.
Note
The parameter can only be set if the "Object type for output" parameter is set on
"1 bit" and the "Operating mode" parameter is set on "Standby" or "ECO".
11.7.17.8
Send frost object
Options:
Deactivated
Activated
■
Deactivated:
– No telegram is sent via object "Sx: frost operating mode" at the press of the operating
mode switchover button.
■
Activated:
– A telegram is sent via object "Sx: frost operating mode" at the press of the operating
mode switchover button.
– The telegram that is sent, always has the inverted value of the value sent last. This
means that "0" or "1" is sent (toggle mode) alternately via object "Sx: frost operating
mode" at each press of the button.
The parameter is used to specify whether a telegram is sent on the bus via the 1-bit
communication object "Sx: frost operating mode" when the operating mode switchover button is
pressed. This may be necessary for switching the linked room temperature controller (RTC) into
a defined operating mode.
Note
The parameter can only be set if the "Object type for output" parameter is set on
"1 bit" and the "Operating mode" parameter is set on "Comfort", "Standby" or
"ECO".