Description of application and parameters
Application "CO2 sensor"
Product manual 2CKA001473B9679
│160
11.5.19 Settings — Value below threshold 1 (-255) for output format byte
Options:
0-255
If the parameterised value of the threshold is undershot, a defined parameterised value is sent
on the KNX bus to reset the event that occurred beforehand. E.g. a fan is activated when the
threshold is undershot to supply the room with fresh air. When the change of air has occurred
and the CO2 concentration has again dropped below the threshold value, the fan is switched
off.
Notice
The parameter is available only when parameter "Control value output format" is
set on "Byte".
11.5.20 Settings — Value below threshold 1 (-64) for output format scene
Options:
1-64
If the parameterised value of the threshold is undershot, a defined parameterised value is sent
on the KNX bus to reset the event that occurred beforehand. For example, a fan is activated
when the threshold is undershot to supply the room with fresh air. When the change of air has
occurred and the CO2 concentration has again dropped below the threshold value, the fan is
switched off.
Notice
The parameter is available only when parameter "Control value output format" is
set on "Scene".