Description of application and parameters
Application "RTC"
Product manual 2CKA001473B9679
│109
11.4.48 Basic stage cooling - PWM cycle cooling (min)
Options:
Setting option between 1 - 60 minutes
In PI PWM, On/off the control value percentage values are converted into a pulse-interval
signal. This means that a selected PWM cycle will be divided into an on-phase and an off-phase
based on the control value. Accordingly, a control value output of 33% in a PWM cycle of 15
min. results in an On-phase of five minutes and an Off-phase of 10 min. The time for a PWM
cycle can be specified here.
NOTE
This parameter is only available when the "Control value type" parameter is set
on "PI PWM, On/Off“.