TROU BLES HO OTING
GENERAL TRO UBLES HOO TING
4JNO0 0030 8 A
55
Problem
Solution
In exceptional cases where a reboot does not fix the problem then the de-
vice must be reset. Either
Set Factory Defaults
(soft reset function) or
Hard Reset
options can be utilized.
Status: “Network Manager
Queue Full”
Slow down the scan rate of the host system (the network queue can store
100 messages and can be overloaded if scanning occurs too quickly).
Modbus Exception
Verify Modbus register addresses.
Verify WirelessHART field device, adapter or wired HART device supports
the command.
Trying to read data from unmapped register will result in exception.
Trying to read data from a device during handshaking state will result in
exception.
Device connects and discon-
nects
If the device does not have good radio signal, then it can have unstable
connection. This can be seen by looking into RSSI, latency, stability and
number of joins in network statistics page. If the number of joins keep go-
ing up, then add repeater nodes (if possible) to improve network reliability,
stability and availability.
RSSI of the device’s active link should be better than -75dBm.
Unable to connect new de-
vice
If it is not possible to add a new device, make sure that there is remaining
capacity left in the gateway to add new device. To check, login to the net-
work statistics page. Up to 100 devices can connect to AWIN GW120.
Connected devices number can be reduced to 8 if all devices burst 3 mes-
sages simultaneously at 1sec update period.
I/O Schedule Upload Failed
When downloading the devices configuration to a gateway where some
devices are offline will result in this error. This error is followed with a sum-
mary of device(s) which failed. For all other devices, configuration upload
is successful.
Try to bring the offline device online and import again.
Low battery lifetime
If a device shows low battery lifetime then replace its battery by following
the service manual of that device.
Radio signal is weak
Make sure there is clearance around the antenna. Look into the guidelines
for installation of antenna in the antenna used in the setup.
Weak mesh network
Login to the network statistics page and verify that each device can com-
municate to at least 3 neighbors (recommended). If so, the device row will
be color coded green.
If not, make sure that all connected devices are operating as mesh nodes
(i.e., routing enabled). You can verify this by logging into the monitor ac-
count and looking at
Devices Information
page. To enable/disable routing
status the user can use Devices Configuration import file.
Port is closed or device is
unresponsive.
Check that the limits are not reached:
–
Maximum 4 Modbus clients can connect simultaneously.
–
Maximum 10 HART-IP clients can connect simultaneously.
If the limit is not reached, then wait for up to 5 minutes for the service to
restart, port to open.
If the gateway remains in closed state and does not recover itself within
few minutes, then simply reset the device by power cycling.
If the device still retains the error state, then try soft or hard reset.
Summary of Contents for AWIN GW120
Page 1: ... ENERGY INDUSTRIES ABB Wireless Industrial Network AWIN GW120 User Manual ...
Page 2: ......
Page 3: ... ENERGY INDUSTRIES ABB Wireless Industrial Network AWIN GW120 User Manual ...
Page 8: ......
Page 10: ......
Page 12: ......
Page 74: ......
Page 75: ......
Page 76: ... Visit us abb com awin Document Number 4JNO000308 Rev A ...