MODBU S EXCEPTIO N CODES
TROU BLES HO OTING
56
4JNO0 0030 8 A
Problem
Solution
Device is stuck in handshak-
ing state
Reboot the device stuck in handshaking state. If not possible, then reform
network or power cycle the gateway.
Note
: Power cycling the gateway or reforming the network will force all de-
vices to drop off the network and reconnect. This will impact network
availability.
Error Retrieving AP Mote
Data From Network Manager
Wait for System Recovery to automatically initiate system recovery. It is of-
ten seen during the boot up process. If this error is persistent after 10+
minutes of boot up then a power cycle may be required.
Network Manager Has Reset.
Wait for System Recovery to automatically initiate system recovery. It is of-
ten seen during the boot up process or during network configuration. If
this error is persistent after 10+ minutes of boot up then a power cycle
may be required.
8.3
Modbus Exception Codes
The following exception codes are supported.
Table 16: Exception codes
Exception code
Meaning
0x01 ILLEGAL_FUNCTION
No request bytes present.
0x02 ILLEGAL_DATA_ADDRESS
Starting address does not exist in mapping.
0x03 ILLEGAL_DATA_VALUE
Starting register valid, but length of requests spans at least one un-
mapped register.
WirelessHART device is disconnected in simplified in mapping.
0x06 SLAVE DEVICE BUSY
Slave is engaged in processing another command. Retry later.
This can happen when:
–
The data is stale. This can be either because the data is old, or be-
cause the device is responding with a non-successful response
code.
–
There is an update to the Modbus mapping in progress.
0x0b GATEWAY TARGET DEVICE
FAILED TO RESPOND
Indicates that no response was obtained from the target device.
This can happen when:
–
Device is disconnected.
–
Sending request to WirelessHART network failed.
To avoid Modbus exception notification, read each individual device data inde-
pendently. In a case of device disconnection, if you try to read data from multi-
ple devices in one block read, it will result in complete Modbus block read error.
Summary of Contents for AWIN GW120
Page 1: ... ENERGY INDUSTRIES ABB Wireless Industrial Network AWIN GW120 User Manual ...
Page 2: ......
Page 3: ... ENERGY INDUSTRIES ABB Wireless Industrial Network AWIN GW120 User Manual ...
Page 8: ......
Page 10: ......
Page 12: ......
Page 74: ......
Page 75: ......
Page 76: ... Visit us abb com awin Document Number 4JNO000308 Rev A ...