![ABB Arc Guard System TVOC-2 Installation And Maintenance Manual Download Page 76](http://html.mh-extra.com/html/abb/arc-guard-system-tvoc-2/arc-guard-system-tvoc-2_installation-and-maintenance-manual_3045239076.webp)
Technical data
74
Optical inputs and outputs
Optical detectors
10 inputs (without extensions)
Current signal from CSU
2 inputs X21, X22 (optical)
Forward current signal to another Arc Monitor
1 output: X1.23 (optical)
Trip contacts (K4, K5, K6)
Solid state contacts
3 NO solid state type IGBT
Rated voltage 250 V AC/DC
250 V AC/DC
Make and carry for 0.2 s
30 A
Make and carry for 1 s 0.15% duty ration
10 A
Breaking capacity
250 V
1.5 A
AC - 15
250 V
1 A
DC - 13
110 V
3 A
DC - 13
48 V
3A
DC - 13
Reinforced insulation between separate contacts.
Voltage drop 5 V 30 A, 3 V 3 A, 2 V 10 mA
Off state current < 1 mA at 250 V
Min. recommended load current 10 mA
Signal relay (K2, K3)
Manual or auto resetable
2 CO gold-plated contacts
Rated voltage
250 V AC/DC
Continous carry I
th
5 A
Make and carry for 0,2 s
30 A
Make and carry for 3 s 10% duty ratio
15 A
Breaking capacity
250 V
3 A
AC - 15
250 V
0,3 A
DC - 13
110 V
0,6 A
DC - 13
48 V
2 A
DC - 13
Reinforced insulation between separate contacts
I
th
= 5 A
Min switching load:
1 mA at 5 V DC with contacts not used for switching current
> 0.5 A if inductive/capacitive load before.
Internal Relay Fault (IRF, K1)
Self supervision alarm relay
1 CO gold-plated contact
Rated voltage
250 V AC/DC
Continious carry I
th
5 A
Make and carry for 3 s
8 A
Breaking capacity
250 V
1,5 A
AC - 15
250 V
0,15 A
DC - 13
110 V
0,3 A
DC - 13
48 V
0,5 A
DC - 13
Reinforced insulation between separate contacts.
I
th
=
5 A
Min switching load:
1 mA at 5 V DC with contacts not used for switching current
> 0.5 A if inductive/capacitive load before.
Summary of Contents for Arc Guard System TVOC-2
Page 1: ...Arc Guard System TVOC 2 Installation and maintenance guide ...
Page 2: ......
Page 8: ...6 ...
Page 10: ...About Arc Guard System 8 ...
Page 54: ...Installation 52 ...
Page 74: ...Human Machine Interface functions 72 ...
Page 82: ...Technical data 80 ...
Page 89: ......