![ABB Arc Guard System TVOC-2 Installation And Maintenance Manual Download Page 75](http://html.mh-extra.com/html/abb/arc-guard-system-tvoc-2/arc-guard-system-tvoc-2_installation-and-maintenance-manual_3045239075.webp)
Technical data
73
Chapter 8: Technical data
Common technical data
Overvoltage category
III
pollution degreee
3
Power supply
Rated operation voltage Ue
100 -250 V DC
100-240 V AC 50-60 HZ
Rared insulation voltage Ui
250 V with reinforced insulation
Rated impulse withstand voltage Uimp
4 kV
Output contacts
Contact rated voltage with reinforced insulation between different contacts
Terminals
Description
Ui
Ue
Uimp
11, 12, 13
IRF signal
250 V
250 V AC 50-60 HZ, 250 V DC
4 kV
21, 22, 23
Signal relay
250 V
250 V AC 50-60 HZ, 250 V DC
4 kV
31, 32, 34
Signal relay
250 V
250 V AC 50-60 HZ, 250 V DC
4 kV
43, 44
Trip contact
250 V
250 V AC 50-60 HZ, 250 V DC
4 kV
53, 54
Trip contact
250 V
250 V AC 50-60 HZ, 250 V DC
4 kV
63, 64
Trip contact
250 V
250 V AC 50-60 HZ, 250 V DC
4 kV
73, 74
50 V
50 V DC
0.5 kV
Environmental specifications
Permissible ambient temperature in operation
- 25 to + 55
°C
Permissible ambient temperature in transportation
and storage
- 25 to + 70°C
Humidity
Maximum 95%
Altitude
2000 meter above sea level
Degree of protection
IP20 Arc Monitor
IP54 HMI front side
Safety parameters for application according to IEC61508
Life time
10 years
PFD
3.49 x 10
-03
Summary of Contents for Arc Guard System TVOC-2
Page 1: ...Arc Guard System TVOC 2 Installation and maintenance guide ...
Page 2: ......
Page 8: ...6 ...
Page 10: ...About Arc Guard System 8 ...
Page 54: ...Installation 52 ...
Page 74: ...Human Machine Interface functions 72 ...
Page 82: ...Technical data 80 ...
Page 89: ......