Installation
42
Manual/Auto reset
configuration
The signal relays K2 and K3 can be configurated to react as trip contacts
(auto reset) or to be de-energized by manual reset on the HMI.
Configuration Auto reset, set DIP switch 6 to position ON.
Configuration Manual reset, set DIP switch 6 to position 0.
Detector
K
4-6
K
2-3
250 ms
O
N
1 2 3 4 5
6
7 8
Detector
K
4-6
K
2-3
250 ms
O
N
1 2 3 4 5
6
7 8
Manual reset