362 Parameters
Selects the source of actual value 1 when
.
Not selected
None.
0
). -
Defines the mapping between parameters and holding
registers in the 400101…465535 Modbus register range.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Mode 0
16-bit values (groups 1…99, indexes 1…99):
Register address = 100 × parameter group +
parameter index. For example, parameter 22.80 would be
mapped to register 2200 + 80 = 402280.
32-bit values (groups 1…99, indexes 1…99):
Register address = 200 × parameter group +
2 × parameter index. For example, parameter 22.80 would be
mapped to register 4400 + 160 = 424560.
0
Mode 1
16-bit values (groups 1…255, indexes 1…255):
Register address = 256 × parameter group +
parameter index. For example, parameter 22.80 would be
mapped to register 5632 + 80 = 405712.
1
Mode 2
32-bit values (groups 1…127, indexes 1…255):
Register address = 512 × parameter group +
2 × parameter index. For example, parameter 22.80 would be
mapped to register 11264 + 160 = 411424.
2
Selects in which order 16-bit registers of 32-bit parameters
are transferred.
For each register, the first byte contains the high order byte
and the second byte contains the low order byte.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
HI-LO
The first register contains the high order word, the second
contains the low order word.
0
LO-HI
The first register contains the low order word, the second
contains the high order word.
1
Activates fieldbus communication monitoring separately for
each control location (see section
The parameter is primarily intended for monitoring the
communication with EFB when it is connected to the
application program and not selected as a control source by
drive parameters.
0000b
0000b…0111b
EFB communication monitoring selection.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Value
0
Ext 1
1 = Communication monitoring active when Ext 1 is being used.
1
Ext 2
1 = Communication monitoring active when Ext 2 is being used.
2
Local
1 = Communication monitoring active when local control is being
used.
3…15
Reserved
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...